ensto LYNX 3400 Installation And Operation Manual

ensto LYNX 3400 Installation And Operation Manual

Directional and polyphase current fault detectors for mv underground networks

Advertisement

Quick Links

LYNX 3400
Installation and operation
manual for directional and polyphase
current fault detectors for MV
underground networks
Ed. 06.2019 V1
Ref: 72789_a / 2009363

Advertisement

Table of Contents
loading

Summary of Contents for ensto LYNX 3400

  • Page 1 LYNX 3400 Installation and operation manual for directional and polyphase current fault detectors for MV underground networks Ed. 06.2019 V1 Ref: 72789_a / 2009363...
  • Page 2 Ensto Novexia declines all liability for any property damage or personal injury caused by poor installation, mishandling, or failure to comply with safety recommendations.
  • Page 3: Table Of Contents

    Introduction................... 4 1.1. Product purpose ............... 5 1.2. General characteristics ............. 5 1.3. List of equipment required for installation ........ 8 (not supplied by Ensto Novexia) Installation ....................9 2.1. Unpacking and handling instructions ........10 2.2. Installation operations ............. 10 2.3.
  • Page 4: Introduction

    Introduction 1.1. Product purpose 1.2. General characteristics 1.3. List of equipment required for installation (not supplied by Ensto Novexia) LYNX 3400 72789_b NX2009363 manual...
  • Page 5 1.1. Product purpose LYNX 3400 fault detectors are designed to be installed on the underground sections of MV networks earthed by means of a limiting coil. The detector enables the following aims to be achieved: • Improving detection performance • Counting faults and changing the operation of auxiliary contacts •...
  • Page 6 100 % 2 g - Vibration resistance (IEC 68-2-6 & 68-2-29) IP30 - IK07 - Protection rating - Overall dimensions 289 x 200 x 92 mm - Device mass (excluding cables) 1.1 kg LYNX 3400 72789_b NX2009363 manual...
  • Page 7 Current sensors Cores Remote indication Voltage sensors Climatic conditions • Operation • Storage Normal operating temperature: Storage temperature: -25 to +70°C -15 to +55°C Relative humidity: 10 to 100% Relative humidity: 10 to 100% 92.5 LYNX 3400 72789_b NX2009363 manual...
  • Page 8 1 Lynx-indicator light housing cable LSH20 type battery, one per case with an LV power supply and two per stand- alone case Standard equipment enabling the device to be wall-mounted (screws and wall plugs) is not supplied by Ensto Novexia. LYNX 3400 72789_b NX2009363...
  • Page 9: Unpacking And Handling Instructions

    2. Installation 2.1. Unpacking and handling instructions 2.2. Installation operations 2.3. External connections LYNX 3400 72789_b NX2009363 manual...
  • Page 10 Open the box and check in relation to the order. 2.2. Installation operations Installing the LYNX 3400 case The LYNX 3400 case is fixed to a flat wall using the following accessories (not supplied by Ensto Novexia): - 4 slotted head screws Ø4.5 X L 35 mm - 4 wall plugs Ø6 L 30 mm...
  • Page 11: External Connections

    2.3. External connections Connecting the CORES (without medium voltage) The current probes used with the LYNX 3400 are splitted core current sensors with a lever clasp on a resin-coated core. Ratio 1/500. The assembly uses three identical cores detecting: - single-phase faults on the earth...
  • Page 12 The wires for each core are connected using a coded 2-contact MATE-N- LOCK connector. A 4x1.5mm² U1000RO2V type cable equipped with female MATE-N- LOCK connectors is supplied for connecting cores to the LYNX 3400's J2 terminal block. Insert the stripped end with end sleeves into the LYNX's cable grommet.
  • Page 13 - Pass the cable end through the appropriate cable gland (refer to page 7) - Connect to terminal strip J1 by doubling the wires in the terminal strip Important!!! In all cases you must restart the calibration procedure for all detectors (refer to page 19) LYNX 3400 72789_b NX2009363 manual...
  • Page 14 Connecting the external indicator light housing The LYNX 3400's indicator light housing has red and green lights. It is supplied with a 3X1.5mm² U1000RO2V type cable. Position the indicator light with the cable gland facing downwards. Connect the J9 terminal block as follows:...
  • Page 15 The LYNX 3400's normal power source is low voltage 230 V, which is available on site. The LV is supplied to the LYNX 3400 by a 2 x 1.5mm² U1000RO2V type cable – not supplied. LYNX 3400s does not need to be connected to the neutral earth.
  • Page 16: Commissioning

    Commissioning 3.1. Points to be checked before commissioning 3.2. List of commissioning operations 3.3. Operational tests LYNX 3400 72789_b NX2009363 manual...
  • Page 17 3.1. Points to be checked before commissioning LYNX 3400 72789_b NX2009363 manual...
  • Page 18 Configuring the network's MV voltage To take into account the network's MV voltage, the configuration of the voltage is carried out by the inverter ST2. Medium voltage 15 kV Medium voltage 20 kV 20 kV: factory setting position LYNX 3400 72789_b NX2009363 manual...
  • Page 19: Operational Tests

    Configuring the fault signaling delay A fault appearing on the network is signaled by the LYNX 3400 only if it causes the disappearance of the MV voltage after a configurable time notably allowing to avoid the activation of the signaling during the reclosing cycle.
  • Page 20 Launch of a LYNX 3400 Test To check the operation of the detector a press on the BP "Test" (BP4) starts the test procedure. If the LYNX 3400 is equipped with a display, it indicates "TEST". Both TS contacts close and the Red and Green LEDs flash on the Lynx board and the external LED for 1minute.
  • Page 21: Operation

    Operation 4.1. Function by function description 4.2. Commands, tests, configurations - upgrades with new functions LYNX 3400 72789_b NX2009363 manual...
  • Page 22 4.1. Function by function description The LYNX 3400 Detector is a fault detector for underground MV network of 15kV or 20kV voltage based on the Directional principle ie a simultaneous monitoring of residual current and voltage. It is in the form of a mono-card mounted in a housing designed to work inside a station The current signals are derived from 3 Tore type ITI sensors with a ratio of 500/1.
  • Page 23 The three green, red and polyphase counters are displayed alternately for 1s (total duration). The displayed value "xxxx" of a counter is 0000 to 9999. To start the display procedure press the BP "display counters" (BP3). LYNX 3400 72789_b NX2009363 manual...
  • Page 24 BP1. - 1 x 250 mA fuse, size 5 x 20 mm, protects the LV power supply (1 spare fuse is available in the box). LYNX 3400 72789_b NX2009363...
  • Page 25 • Test See § 3.3 Installation page 19 • Configurations See § 3.2 Installation page 18 LYNX 3400 72789_b NX2009363 manual...
  • Page 26: Maintenance

    Maintenance 5.1. Preventive 5.2. Corrective LYNX 3400 72789_b NX2009363 manual...
  • Page 27: Preventive

    5.1. Preventive Deactivating the LYNX 3400 - Open the cover by unclipping it. - Disconnect the integrated power supply: Either the battery via J10,or the supercapacitor via J11 - If it has not been switched off externally before opening the cover, switch off the 230V power supply by opening the fuse holder.
  • Page 28: Corrective

    The 15-year usable life of supercapacitors means that they do not need to be replaced. 5.2. Corrective Should the equipment stop working, return the electronic board to Ensto Novexia. To do this, you need to: * Deactivate the case (see Page 27)
  • Page 29: Technical Assistance

    210, rue Léon Jouhaux - BP 10446 FR - 69656 Villefranche-sur-Saône Cedex Tel.: +33 (0)4 74 65 61 60 Mobile: +33 (0)6 08 93 26 31 You can also contact us by e-mail at infos.novexia@ensto.com Ensto Novexia is also able to provide customized training.
  • Page 30: End Of Product Life Cycle

    End of product life cycle For any question relating to the end of the product’s life, contact the after-sales service with the technical details of the sub-assemblies and/or products to be recycled. LYNX 3400 72789_b NX2009363 manual...