Honeywell Notifier FCM-1 Installation And Maintenance Instructions page 2

Supervised control module

Advertisement

FIGURE 1A:
FIGURE 1B. JUMPER LOCATION:
J1
C1059-00
FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70.
LISTED FOR FIRE PROTECTION
WITH BATTERY BACKUP.
(–)
)
( +
MODULE POLARITIES ARE
SHOWN IN ALARM
(–)
(–)
47K EOL
RESISTOR
ELR-47K
)
( +
)
( +
UL LISTED EOL
TO NEXT CONTROL MODULE OR
RELAY SHOWN
END-OF-LINE RELAY. ONE RELAY
ENERGIZED
REQUIRED FOR EACH CIRCUIT. SOME
24 VDC COIL
CONTROL PANELS HAVE RELAY BUILT
EOLR-1
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
NO-460-004
FIGURE 2A. MODULE MOUNTING
FIGURE 2B:
WITH BARRIER:
C0910-00
CONNECT MODULES TO
LISTED COMPATIBLE CONTROL
PANELS ONLY
(–)
CONTROL
)
( +
MODULE
(–)
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
)
( +
TWISTED PAIR
IS RECOMMENDED
(–)
(+)
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
2
FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER
NFPA 70. LISTED FOR
FIRE PROTECTION WITH
BATTERY BACKUP.
EOL RESISTOR
IS INTERNAL
AT TERMINALS
8 AND 9
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C1070-00
FIGURE 5. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y:
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
FROM PANEL
USE ONLY MODELS AA-30, AA100 OR
OR PREVIOUS
AA-120. AMPLIFIER MUST PROVIDE
DEVICE
WIRING SUPERVISION PER NFPA.
47K EOL
RESISTOR
ELR-47K
TO NEXT
DEVICE
SUPERVISION
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0947-00
I56-3500-008
NO-460-004
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10
& 11. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
)
( –
CONTROL
)
( +
MODULE
MODULE POLARITIES ARE
SHOWN IN ALARM
)
( –
)
( –
)
( +
)
( +
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
ALL WIRING SHOWN IS SUPERVISED
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
AUDIO CIRCUIT
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
CONTROL
MODULE
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
3
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL
PANELS ONLY
)
( –
FROM PANEL
OR PREVIOUS
)
( +
DEVICE
)
( –
)
( +
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
(–)
TO NEXT
(+)
DEVICE
AND POWER LIMITED
C0948-00
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS
SUPERVISED AND POWER LIMITED
TO NEXT
DEVICE
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION.
C0949-02
I56-3500-008