1. Visual control
Unit dry inside
Gray and red hose
Not clamped, fitted with proper inclination and outlet in pit without risk of ending up under water
Green hose
Not clamped, fitted with proper inclination and outlet outside pit
Action plan:
Unit wet inside
Hose examination failed
2. Check and classify the filter status.
For assistance regarding classification see Appendix 1.
Filter clean
Filter emptied
Action plan:
Filter dirty
Filter not emptied
3.
C heck and classify pit status.
Pit clean
Algaes in the water
Ice on surface
Comment/Action:
4. Check the water level in the pit .
Measured water level in mm
Action plan:
Water level over 300mm
5.
If required, filter replacement and calibration of the measuring cell through the exchange
as described in appendix 2 and 3.
Filter exchange registrered
Calibration of measuring cell registered
Unit started manually and discharged started through GREEN hose
Important!
Registration of filter replacement and calibration of the measuring cell as well as manual start and
reset of the device can be done by:
1. Scan unit QR code, enter the access code and then follow the instructions, appendix 4.
2. Contact support via SMS, telephone or email
Pass
Pass
C ontact your support.
C ontact your support.
Filter dirty
Filter not emptied
C ontact your support for approval of a filter change.
C ontact your support for approval of a filter change.
Cleaning necessary
Oil on surface
Pit bottom frozen
C ontact your support.
Unit ID:
Date:
Unit wet inside
Fail
Fail