All commitments on the part of Siemens are contained in the respective sales contract which also contains the complete and solely applicable warranty conditions. These warranty conditions in the contract are neither extended nor limited by the contents of this Manual.
24V/150 W power pack V24230-Z6-A1 Covers for battery poles C24243-A100-C12 Scope of Delivery Installation Instructions ACC-010 Advanced Central Contr. RIM-010 DRI 24VDC 24V/150 W power pack Enclosure base plate Enclosure shell Installation kit Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
Protection rating (EN60529) IP30 Rel. humidity F (< 95%) Environmental class Design Cabinet dimensions (W x H x D) in 500 x 750 x 200 Color RAL 7035, light gray Material Steel sheet Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
The AFO5100 (Output Point Module) can be installed on top of the ACC using the included spacer bolts as well. The fully expanded configuration may not exceed the max. ourpur power of the power supply. Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products...
An AFO5100 or an AFI5100 can be installed on top of the ACC as well. The DIN rail mount is generously dimensioned and thus can accommodate an additional 150 W power supply. The cabinet is prepared for max. two 12 V/25 Ah batteries. Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
Possible configurations at max. power consumption of the components: Power pack(s) DRIs AFI5100 AFO5100 When making configurations, the max. power consumption of the system (readers, door locks) must be taken into account. Fig. 2 Installation plate Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
Check all system functions. If necessary, analyse and eliminate errors (troubleshooting). Place installation instructions, inventory list, configuration and structure plans into the controller. Carry out acceptance procedure. Close cabinet and attach seal. Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
ACC to the base plate and replace these with the corresponding spacer bolts. Remove the AFI5100 or the AFO5100 from the package and screw to the spacer bolts. Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products...
Rest Power OK (gn) Battery malfunction (yl) Sensor malfunction (yl) Slave Master Battery temperature sensor Siemens Matsushita NTC K164/4,7k/K B57164-K472-K PE / FPE Maintenance-free lead-gel batteries 2 x 12 V Battery fuse F2 for output X8/10 T6,3AH250V 5 x 20...
External loads have to be protected with a fuse that matches the conductor cross- section. For example, a line with a cross-section of 2.5 mm² can be protected with max. 20A. Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
The PE is connected with the device via the grounding terminal. On the other side of the grounding terminal, a green-yellow line leads to the power pack. This ensures proper protection is provided (protecting health and life). Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
The green-yellow lead is attached to the grounding terminal on the rail mount. From there a cable leads to the PE connection of the power supply. Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products...
(document number: A24205-A335-A155). AFI5100/AFO5100 Connection A detailed description of connecting the AFI5100 and AFO5100 is listed in the following documents: IPM User Manual (document number: A24205-A335-B169) OPM User Manual (document number: A24205-A335-B170) Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...
χ = spec. conduct. value for copper and 0.5 V voltage drop along line: Ω ⋅ A = Lead cross-section in mm U = Voltage in V ⋅ ⋅ ..χ ⋅ ⋅ Siemens Building Technologies A24205-A335-B219.doc Fire & Security Products 08.2004...