Description

Siemens Building Technologies
Fire & Security Products
The AC5160 is a cabinet for the basic components of the SiPass access control
system. This cabinet can be expanded with additional components.
The Advanced Central Controller (ACC) is one of the basic components. It is the
central analysis unit for the access control system. This unit is connected with the
input/output boards via the field level network (FLN). The ACC is equipped with
four FLNs. TCP/IP is used to link to the SiPass Server.
The Dual Reader Interface (DRI) is a door module including all necessary inputs
and outputs.. Support of up to two card readers, door monitoring inputs (e.g. door
frame contact) and associated outputs (e.g. door latch). The FLN connects the DRI
to the ACC. The AC5160 includes 2 DRIs. Four additional DRIs can be installed
into the AC5160 cabinet.
The basic AC5160 model is equipped with a 24V/150 W power supply. If
necessary, an additional power supply can be placed in the AC5160 and
connected in parallel to the existing power pack (master/slave operation).
The AC5160 can be equipped with two 12-volt batteries of a capacity up to 25 Ah
each. These are connected to and charged by the power supply. In the event of a
power failure, the system is kept online by the batteries. The Batteries are not
included in the delivery scope.
The Input Point Module (AFI5100) is an input board with 32 inputs and 5 outputs.
This module also connects to the ACC via the FLN. The AFI5100 is not part of the
basic configuration.
The Output Point Module (AFO5100) is an output board especially designed for
elevator access control but can also be used for general purposes. The module
features 16 inputs and 16 outputs and is also connected to the ACC via FLN. The
AFO5100 is not part of the basic configuration.
Please refer to the corresponding user guide for a detailed description of these
modules.
The basic configuration – consisting of power supply, ACC, and two DRIs – can be
expanded by the previously mentioned components. The following configurations
are possible:
Six DRI's in total.
The AC5160 provides 5 installation slots for simple installation of the DRIs. This
means that one DRI needs to be installed on top of another DRI when
expanding the basic configuration to the maximum of 6 DRIs.
Additional 150 W power power supply (see chapter 5.3).
AFI5100.
The AFI5100 (Input Point Module) can be installed on top of the ACC using the
included spacer bolts. The fully expanded configuration may not exceed the
max. output power of the power supply.
AFO5100.
The AFO5100 (Output Point Module) can be installed on top of the ACC using
the included spacer bolts as well. The fully expanded configuration may not
exceed the max. ourpur power of the power supply.