2. SYSTEM (basic) ELECTRICAL RATINGS/SPECIFICATIONS

INPUT POWER
INPUT CURRENT DRAIN
GAS VALVE RATING
OPERATING TEMPERATURE
FLAME SENSITIVITY
FLAME FAILURE RESPONSE TIME 0.8 seconds maximum
TYPE of GASES
SIZE (length x width x height)
WEIGHT
ENCLOSURE
TRIES FOR IGNITION
TRIAL FOR IGNITION PERIOD
INTER-PURGE
C. HSI (Hot Surface Ignition) SYSTEM OPERATION

1. HSI SYSTEM OPERATION

a. The HSI Module's "red" indicator light will light for up to approximately five (5) seconds
(self check routine).
If the HSI Module's "red" indicator light
stays on or flashes continuously, then the
HSI module is wired incorrectly or has failed.
b. Start the drying cycle.
c. The Hot Surface Ignitor will turn on. After
approximately four (4) seconds the Hot
Surface Ignitor will shut off and the gas
valve will be energized. The flame should
now be established.
d . With the burner flame on, remove the flame sensor wire from the S2 terminal of the HSI
module. The burner flame must shut off immediately.
e. Stop the drying cycle, with the Flame Sensor removed, restart the drying cycle.
CONTROL: 18-30 VAC 50/60 Hz
300 mA @ 24 VAC with GAS VALVE RELAY ENERGIZED
(control only)
2.0A @ 24 VAC
0 °F (fahreheit) to 160 °F (fahreheit)
0 °C (Celsius) to 71 °C (Celsius)
.7 A minimum
NATURAL, L.P. (liquid propane), or manufactured
4.23" x 3.23" x 1.63" (with cover)
10.75 cm x 8.21 cm x 3.97 cm (with cover)
5 ounces (nominal)
145 grams (nominal)
GRAY (Noryl N-190) FIRE RETARDANT PLASTIC
three (3)
4 seconds
3.5 seconds
5