Immersion Heaters
CX Series
Installation, Operation, & Maintenance Instructions
For CE/ATEX and IECEx Models. Models with
Increased Safety (Type eb) Protection Method
Special Notes
CAUTION. This document presents the minimum requirement pertaining
to the installation, operation, and maintenance of the respective
equipment as required by the manufacturer only. Any additional
CAUTION
considerations, including but not limited to any design consideration,
in-service inspection, and fitness-for-service assessment for all pressure
boundary components to meet any safety principles and local jurisdictional
regulatory requirements, shall be the responsibility of the user.
ELECTRIC SHOCK HAZARD. All electric heating equipment installations
must be performed by qualified personnel in accordance with the local
electrical codes and standards and must be effectively grounded to
CAUTION
eliminate shock hazard.
FIRE/EXPLOSION HAZARD FOR EXPLOSIVE ATMOSPHERE HEATERS.
This heater shall be used with protection controls as follows:
WARNING
Liquid Immersion Applications
a.
Liquid level control to maintain all the heating elements totally
immersed at all times, in conjunction with temperature controls to limit
the liquid temperature below the maximum allowable process design
temperature.
b. Terminal box internal surface temperature control to limit the surface
temperature of the terminal box
c.
Heater flange surface temperature control to limit the surface
temperature of the flange.
d. Heating elements sheath temperature controls to limit to the maximum
allowable sheath design temperature
e.
Earth fault or earth leakage current protection device to protect against
arcing and sparking during an earth fault.
Gaseous and/or vapour phase immersion applications
a.
Heating elements sheath temperature controls to limit to the maximum
allowable sheath design temperature.
b. Terminal box internal surface temperature control to limit the surface
temperature of the terminal box
c.
Heater flange surface temperature control to limit the surface
temperature of the flange.
d. Earth fault or earth leakage current protection device to protect against
arcing and sparking during an earth fault.
THS3001-1020 Printed in Canada
ISO 9001

Advertisement

loading
Need help?

Need help?

Do you have a question about the CX Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Caloritech CX Series

  • Page 1 Immersion Heaters CX Series ISO 9001 Installation, Operation, & Maintenance Instructions For CE/ATEX and IECEx Models. Models with Increased Safety (Type eb) Protection Method Special Notes CAUTION. This document presents the minimum requirement pertaining to the installation, operation, and maintenance of the respective equipment as required by the manufacturer only.
  • Page 2 Fire/Explosion Hazard. Do not exceed the ratings of the flange as listed in ANSI BI6.5. In case of code stamped of registered heater, do not exceed the rating as stated in the data report and/or registration documents. Do WARNING not operate the heater in the presence of combustible gases, vapours, dusts or fibres unless the heater is specifically marked for the hazardous location and heater operating temperature does not exceed the temperature code rating.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS A. Diagrams ..........4 B. Description ........6 C. Installation .........7 D. Operation ...........8 E. Maintenance ........8...
  • Page 4: Diagrams

    DIAGRAMS Immersion Heater - Round Box (IP66) Stilted ELEMENT SUPPORT SHEATH TEMPERATURE SENSOR (KEEPER) TERMINAL BOX TEMPERATURE SENSOR (THERMOCOUPLE OR RTD) (THERMOCOUPLE OR RTD) INCREASED SAFETY TERMINAL BOX - ROUND (RATED IP66) AVAILABLE IN PAINTED STEEL OR STAINLESS STEEL WIRING CONNECTION HUBS HEATING ELEMENT (METRIC OR IMPERIAL) INCREASED SAFETY...
  • Page 5 Immersion Heater - Square or Rectangular Box (IP64) - Stilted ELEMENT SUPPORT FLANGE TEMPERATURE SENSOR SHEATH TEMPERATURE SENSOR (KEEPER) (THERMOCOUPLE OR RTD) (THERMOCOUPLE OR RTD) TERMINAL BOX TEMPERATURE SENSOR (THERMOCOUPLE OR RTD) INCREASED SAFETY TERMINAL BLOCKS HEATING ELEMENT WIRING CONNECTION HUBS - AVAILABLE IN STEEL, STAINLESS (METRIC OR IMPERIAL) INCREASED SAFETY...
  • Page 6: Description

    DESCRIPTION 6. For and/or IECEx Certification: Immersion heaters for liquid service are designed for operation only while completely immersed in liquids. Never allow the II 2 G Ex eb IIC T6...TI Gb heating elements to be exposed while energized or failure will result.
  • Page 7: Installation

    INSTALLATION CAUTION Heaters with overtemperature CAUTION Use copper conductors only devices require specific installation orientation. with sufficient current carrying capacity for CAUTION Overtemperature devices are required to be the heater circuit load and in accordance CAUTION installed in accordance with local codes and with the local electrical code.
  • Page 8: Operation

    14. The heaters must be protected against abnormal earth IT Systems: fault and earth leakage current. Depending on the electrical An insulation monitoring device designed to trip when the power system, the following protection device must be insulation between any phase of the electrical power supply installed with the heater: to ground is less than 50Ω/V.
  • Page 9 NOTES...
  • Page 10 NOTES...
  • Page 11 NOTES...
  • Page 12 PLEASE ADHERE TO INSTRUCTIONS IN THIS MANUAL Failure to do so may be dangerous and may void certain provisions of your warranty. For further assistance, please call 24hr hotline: 1-877-325-3473 (U.S.A. and Canada) Please have model and serial numbers available before calling. WARRANTY: No warranty applies to paint fi nishes except for manufacturing Under normal use the Company warrants to...