INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR
ELECTRIC SHOCK HAZARD. All electric heating equipment installations must be performed
by qualified personnel in accordance with the local electrical codes and standards and must
be effectively grounded to eliminate shock hazard.
FIRE/EXPLOSION HAZARD. Do not exceed the ratings of the flange as listed in ANSI B16.5. Do not
operate the heater in the presence of combustible gases, vapours, dusts or fibres unless the heater is
specifically marked for the hazardous location and heater operating temperature does not exceed the
temperature code rating. Corrosion of the sheath could result in a ground fault which, depending upon
the fluid being heated, could cause a fire or an explosion.
FIRE HAZARD. If a thermostat is provided, it is designed for temperature control service only. Since the
thermostat does not fail safe, it should not be used for temperature limiting duty. Wiring to this device is
the users responsibility.
Heaters are capable of developing high temperatures, therefore extreme care should be taken to:
a) use explosion-proof terminal enclosures in hazardous locations;
b) maintain distance between heater and combustible materials.
DESCRIPTION
1.0 Circulation heaters for liquid service are designed for
operation only while completely full with liquids. Never allow the
heating elements to be exposed while energized or failure will
result.
Use the heater only in liquids and at pressures
for which it was designed (unless specifically
designed for non-liquid applications). Normally
copper sheath is recommended in water; steel
or alloy sheath in oil; and the appropriate alloy
sheath for heating gas and chemical solutions.
Check factory for recommendations.
2.0 Circulation heaters are welded pressure vessels with inlet
and outlet connections to allow fluid/gas flow and heat transfer
to a customer fluid.
3.0 Where gasket is required, user must ensure that gasket
surface is clean and dry before installing heater.
DO NOT insulate over the heater flange, stilted area
and terminal enclosure.
4.0 The terminals must be protected at all times from moisture
or vapour. In hazardous locations, explosion-proof terminal
housings must be used. In outdoor locations, moisture resistant
housings are required. It is recommended to use a drip loop to
prevent moisture from entering the terminal box via the wire.
5.0 Protect terminals of heating elements from drippings,
condensation, fumes, spray or any other substance which could
result in element contamination.
Email: info@ccithermal.com
Printed in Canada
TYPE EX – CIRCULATION HEATERS
INSTALLATION
Heaters with over temperature devices require
specific installation orientation.
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing the heater. Failure to
do so could result in personal injury and/or property
damage. All maintenance and installation should
be done by qualified personnel in compliance with
local codes.
FIRE OR SHOCK HAZARD: Moisture accumulation
on the dielectric material of the elements sheath,
corrosion or overtemperature on the heaters could
cause a fault to ground generating arcing and molten
metal. Install proper ground fault protection to
prevent personal injury or property damage.
Heaters are electrical components, designers
are responsible for the proper integration to the
electrical systems, including controls and backup
safety devices.
6.0 Provide adequate space for vertical or horizontal installation.
With horizontal mounting, inlet and outlet must be directed
upwards at 90° from the horizontal.
7.0 Ensure that the circulation heater vessel is properly mounted
on a solid steel or concrete base. For heater removal and
maintenance purposes, user must allow sufficient clearance in
the surrounding area of the circulation heater.
ISO 9001
www.ccithermal.com
Date of Issue: May 2013
Part No. MI416 Rev.10.01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EXC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Caloritech EXC

  • Page 1 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR TYPE EX – CIRCULATION HEATERS ELECTRIC SHOCK HAZARD. All electric heating equipment installations must be performed ISO 9001 by qualified personnel in accordance with the local electrical codes and standards and must be effectively grounded to eliminate shock hazard. FIRE/EXPLOSION HAZARD.
  • Page 2: Operation

    8.0 When insulation is supplied, special care must be taken 18.0 In order to allow for expansion and contraction the use of lock while handling the heater for installations. Failure to do this washers when mounting is not recommended. Apply minimum could compromise the integrity of the metal jacket covering the torque necessary to contain the equipment but still allow for insulating material.
  • Page 3: Maintenance

    Low megohm on heating elements with epoxy or 32.0 Heaters stored for prolonged periods may absorb moisture. Using a 500VDC megger (insulation resistance tester) check the hermetic seals cannot be serviced in the field. value of the insulation resistance to ground for each circuit. Initial Typical resistance values when sealed are 1000 megohm or greater.
  • Page 4 5918 Roper Road, Edmonton, Alberta, Canada T6B 3E1 Phone: (780) 466-3178 Fax: (780) 468-5904 PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL. Failure to do so may be dangerous and may void certain provisions of your warranty. For further assistance, please call: 24 Hr.
  • Page 5: Installation

    Chauffage électrique sur demande INSTRUCTIONS POUR L’INSTALLATION ET L’ENTRETIEN RÉCHAUFFEURS À CIRCULATION – MODÈLE EX RISQUE D’ÉLECTROCUTION. Toutes les installation d’équipment électrique de chauffage doivent être réalisées par un personnel qualifié, conformément aux codes et normes électriques locaux, et doivent être dûment mises à...
  • Page 6 Chauffage électrique sur demande 8.0 Lorsque le chauffe-eau est muni d’un revêtement calorifuge, un soin 18.0 Le montage du chauffe-eau doit être effectué conformément aux particulier doit être apporté lors de sa manutention. Á défaut, cela pourrait spécifications de conception de l’appareil. À défaut, cela pourrait entraîner compromettre l’intégrité...
  • Page 7: Entretien Et Réparation

    Chauffage électrique sur demande RISQUE D’INCENDIE. Pour que le thermoplongeur 32.0 Les thermoplongeurs entreposés pendant de longues périodes fonctionne bien, et pour éviter la surchauffe des peuvent absorber de l’humidité. À l’aide d’un mégohmmètre 500 VDC éléments chauffants, qui pourrait provoquer un incendie (appareil de mesure de résistance de l’isolation), vérifiez la valeur de la ou endommager le thermoplongeur, il faut que le résistance de l’isolation à...
  • Page 8 Chauffages catalytiques au gaz antidéflagrants 5918 Roper Road, Edmonton, Alberta, Canada T6B 3E1 Téléphone: 1 780 466-3178 Télécopie: 1 780 468-5904 VEUILLEZ VOUS CONFORMER AUX INSTRUCTIONS CONTENUES DANS CE MANUEL. Tout manquement à ces dernières pourrait s’avérer dangereux et invalider certaines dispositions de votre garantie.