TORK
Lighting Delay Switch
Model: LDS, LDS-A
INSTALLATION AND USER'S GUIDE
FUNCTION & DESCRIPTION
The Lighting Delay Switch is an accessory to any
TORK maintained contact time switch and is used
to extend the lighting time after the main time
switch turns OFF a lighting circuit. An approximate
1/2 second blink will occur as a warning that the
lighting will go OFF in (user selectable) 1 or 5
minute warning period.
Remote momentary ON/OFF push button switch-
es can be connected to the designated terminal of
the Lighting Delay Switch using low voltage # 18 -
22 AWG twisted pair wires. Pressing the remote
ON button momentarily during the 1 or 5 minute
warning period (before the lights go out) will
extend the time ON for a user selectable 1/2 hour,
1 hour, 1-1/2 hour, 2 hours, 6 hours, 9 hours, or
12 hours. At the end of the extended time a warn-
ing blink will again occur, allowing personnel to
repeat another 1/2 - 12 hour extension if necessary.
Pressing the remote OFF button for 3 to 4 seconds
will terminate the extension of time, and initiate the
warning blink. The lights will turn OFF after the 1 or
5 minute warning period.
When starting up after a power failure (if time
switch is not ON), lighting will be turned ON for 10
minutes. At the end of the 10 minute period a
warning blink will occur. The lights will remain ON
for the 1 or 5 minute warning period. If an exten-
sion of time is required, press the remote ON but-
ton momentarily.
This unit is ideally suited to meet Energy
Conservation construction codes relative to con-
trolled lighting after hours and assures lighting will
go OFF after personnel (i.e. cleaning-staff working
after hours) leave the building.

Advertisement

loading

Summary of Contents for Tork LDS

  • Page 1 INSTALLATION AND USER’S GUIDE FUNCTION & DESCRIPTION The Lighting Delay Switch is an accessory to any TORK maintained contact time switch and is used to extend the lighting time after the main time switch turns OFF a lighting circuit. An approximate...
  • Page 2 OFF, the load will turn OFF after the warning period. SETTING & WIRING DIAGRAM Step 1: Model LDS only. Remove the unit from the plastic track. Mount the plastic track with provided hard- ware only. Do not use other hardware. Snap the unit back into the track.
  • Page 3 tion of the unit to under 1 minute, allowing a check of the wiring and the functions. Step 4: Set the extended time delay for the main load to the appropriate time by adjusting switch #1, 2, and 3. See table for desired timing. Step 5: Set the warning period for 1 or 5 minutes using switch # 4.
  • Page 4 WIRING DIAGRAMS TORK TIME SWITCH OUTPUT TERMINALS MOMENTARY PUSH-BUTTON SWITCH REMOTE INPUT C ON OFF TIME SWITCH INPUT POWER DO NOT APPLY INPUT VOLTAGE MAIN LOAD OUTPUT TERMINALS LOAD CAUTION: Turn power off at main circuit prior to installation or when servicing this unit.

This manual is also suitable for:

Lds-a