MODEL 365A & E365A VIBRASWITCHES
Figure 3-5

Preparation of Conduit Wiring

To avoid unnecessary difficulty in wiring the Vibraswitch, the following procedure should be used:
a. When threading conduit, cut the wires so that all wires project beyond the housing surface approximately 1-1/2"
(38 mm) as shown in Figure 3-5. Do not later pull the wires tight as you will be unable to remove cover holding
the mechanism.
b. Strip wires back 1/4" (6.4 mm) and install solderless terminals.
c. Place the Vibraswitch in position shown in Figure 3-6 and connect wires to corresponding terminals.
d. Flatten wires entering housing against wall on conduit hub side and rotate cover into place, pushing extra wire
into corners near conduit hub.
e. Replace cover bolts, tighten to 75-105 inch lbs (8.5-11.9 Nm).
1-1/2"
(38 MM)
- 8 -
Figure 3-6

Connection of Conduit Wiring

909GF294G