HUMIDIFIER POWER SUPPLY
Underneath the fill solenoid valve on the steam production unit is
the threaded male fitting (V) for the humidifier water supply.
This is already fitted with a plastic hose, diameter 6 mm, for con-
nection to the building's water supply (see figure, point F).
V: Steam production unit - inlet connection (threaded male fit-
ting);
F: Rubber hose, diameter: 6mm.
To supply the humidifier, use drinking water without any chemical
treatment or demineralisation.
The characteristics of the water that supplies the humidifier must
be within the following values:
Characteristic
Mains pressure
Electrical conductivity at 25°C
Phosphate content
Chloride content
Hardness
Size of the impurities
Do not use water treated by demineralisation or softening systems.
A mechanical filter with a mesh finer than 50 _m should be installed.
MINIMUM CROSS-SECTION OF THE POWER CABLES
The cross-section of the power cable must be chosen according
to the length of the cable and the type of installation, based on
the maximum current input of the air-conditioner and so as to
prevent excessive voltage drops (the power supply voltage must
be between ± 10% of the rated value).
The following table shows the minimum recommended cross-sec-
tions for the power cables.
24
English 01/07
Minimum value
1 bar
125 µ S/cm
-
-
-
-
- A backup fuse should be fitted upstream of the power
line for short-circuit current up to 10 kA.
U
I
A
position:V-F
Maximum value
8 bar
1250 µ S/cm
5 mg/l
50 mg/l
40°fH
0.1 mm
U
I
A
ACCURATE AX* - AW*