Dell RapidPower 12-A NEMA power strip Installation Manual page 20

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Cabling 10-A and 12-A Power Strips
10-A and 12-A power strips can be used as power extensions from a UPS (see Figure 1-9).
Figure 1-9. Cabling a 10-A and 12-A Power Strips From a UPS
10-A and 12-A power strips can also be used as power extensions from 16-A, 24/32-A, 32-A, and 40-A PDUs
(see Figure 1-10). Table 1-1 lists the maximum number of power strips that can be used with each PDU.
Table 1-1. Maximum Number of Power Strips per PDU
PDU Model
16-A PDU
24/32-A PDU
32-A PDU
40-A PDU
30-A Three-Phase PDU
60-A Single-Phase PDU
18
Installation Guide
UPS
Maximum Combined
Current per PDU
16 A
24/32 A
32 A
40 A
30 A
60 A
10-A or 12-A
power strip
Maximum Number
of 10-A Power Strips
1
2
4
NA
3
3
rack component
Maximum Number
of 12-A Power Strips
1
2
NA
4
2
3

Advertisement

Table of Contents
loading

Table of Contents