4 | Installation
3.3

Removing the heat exchanger

▶ Close the maintenance shut-off valves [1] and drain [2] of the
Logamax plus GB142.
2
1
Fig. 7
Maintenance shut-off valves
▶ Remove the cable plug from the gas control valve.
Fig. 8
Removing the gas control valve cable plug
▶ Remove both cable plugs [1] from the fan unit.
Fig. 9
Removing the fan unit cable plugs
6 720 810 045 (2013/12)
1
6 720 641 697-007.1TD
6 720 641 697-015.1TD
1
6 720 641 697-016.1TD
▶ Pull both retaining clips [1] on the burner cover to open them and
remove the burner cover with the fan unit and the gas control valve.
1.
Fig. 10 Loosening the retaining clips
▶ Remove the burner [1].
Fig. 11 Removing the burner
CAUTION: electrical short circuit.
To prevent mix-ups, the supply sensor is marked by a
red sleeve on the side of the cable harness.
▶ Disconnect the supply [1], return [2] and safety [3] sensors.
1
Fig. 12 Disconnecting the supply sensor
1.
6 720 641 697-017.1TD
1
6 720 641 697-018.2TD
6 720 641 697-019.1TD
Logamax plus GB142-24/30/45/60