Jakka EVO PH Manual page 27

Heat recovery unit controller
Table of Contents

Advertisement

EVO controller
DP_SUPPLY
91
DP_EXHAUST
92
FLOW_
93
SUPPLY
FLOW_
EXHAUST
94
FAN_
HOURS_H
95
FAN_
96
HOURS_L
B00: CONFIGURATION_FAIL
B01: ANTI_ICE_
ALARMS 2
B02: EXT_AI2_FAIL
97
B03: TD_FAIL
B04: COMM_X570_EDPS_FAIL
B05: COMM_X570_EDPE_FAIL
B06: EDPS_FAIL
B07: EDPE_FAIL
B08: AUTO2_TO_FAIL
B09: MIN_SPEED
PRE-HEAT
98
POST-HEAT
99
TEMP_D
100
101
TEMP_E
221
TEMP_E
1001
TIME_TABLE_SPEED_0**
1002
TIME_TABLE_SPEED_1**
1003
TIME_TABLE_SPEED_2**
1017-
MONDAY-CHANGE-0/7**
1024
1025-1032
TUESDAY-CHANGE - 0/7**
1033-1040
WEDNESDAY-CHANGE - 0/7**
1041-1048
THURSDAY-CHANGE - 0/7**
1049-1056
FRIDAY-CHANGE - 0/7**
1057-1064
SATURDAY-CHANGE - 0/7**
1065-1072
SUNDAY-CHANGE - 0/7**
www.jakkagroup.com
B08: COMM_X531_FAIL
B09: TW_FAIL
B10: TW_LOW
B11: AUTO_TO_FAIL
B12: COMM_X570_DPE_FAIL
B13: COMM_X570_DPE_FAIL
B14: DPSUPPLY_FAIL
B15: DPEXHAUST_FAIL
[Pa]
[Pa]
[m³/h]
[m³/h]
[65536 h]
[h]
[%]
[%]
(0,1°C]
IF CONFIG_FLAGS_1.MODULE_
FLAG = 0 : 0-1-2-3 or TIMER (4)
or AUTO(5)
IF CONFIG_FLAGS_1.MODULE_
FLAG = 1 and PRESS_FLOW_
REG_PRESENT = 0 : 0-100% or
TIMER (101) or AUTO(102)
IF CONFIG_FLAGS_1.MODULE_
FLAG = 1 and PRESS_FLOW_
REG_PRESENT = 1 : 0 - SPEED_
RANGE or TIMER(65634) or
AUTO(65535)
B00-10: TIME - MINUTES
B11-13: SPEED SELECTION
000: TIME_TABLE_SPEED_0
001: TIME_TABLE_SPEED_1
002: TIME_TABLE_SPEED_2
B14-15: TEMPERATUE REG.
ENABLE
00: OFF
01: ON
COMMUNICATION ERROR IN X531 BOARD.
WATER COIL FROST ALARM.
AIR/HUMIDITY QUALITY PROBE TIMEOUT ALARM.
COMMUNICATION ERROR IN X570 BOARD DELIVERY.
COMMUNICATION ERROR IN X570 BOARD EXHAUST.
DELIVERY PRESSURE SENSOR FAILURE.
EXHAUST PRESSURE SENSOR FAILURE.
FOR COP UNIT = PRESSURE VALUE OF DELIVERY FAN SIDE
R
FOR COP UNIT = PRESSURE VALUE OF RETURN FAN SIDE
FOR CAV UNIT = AIR FLOW VALUE OF DELIVERY FAN SIDE
R
FOR CAV UNIT = AIR FLOW VALUE OF RETURN FAN SIDE
R
FAN OPERATION TIME (FAN_HOURS_H * 65536+ FAN_HOURS_L )
R
R
ERROR CONFIG.
ANTI ICE ALARM
R
ERRORE INGRESSO ANALOGICO 2
DEW POINT PROBE LINE FAILURE (TD).
COM. ERROR IN X570 EXTRAFLOW SENSE BOARD DELIVERY.
COM. ERROR IN X570 EXTRAFLOW SENSE BOARD EXHAUST.
R
FAULT X570 BOARD DELIVERY.
FAULT X570 BOARD DELIVERY.
AIR/HUMIDITY QUALITY PROBE ON INPUT 2 TIMEOUT ALARM
UNIT RUN AT MIN SPEED FROM DIGITAL INPUT
PERCENTAGE OF REGULATION PRE-HEATING
R
PERCENTAGE OF REGULATION POST-HEATING
R
AIR TEMPERATURE AFTER COOL COIL IN DEUMIDIFY SYSTEM
R
UNIT_2_DATA
R
UNIT_4_DATA
R
TIMETABLE PROGRAM
R/W
SELECTION TIMETABLE SPEED
R/W
SETTING TIMETABLE IN MINUTES MINUTES FROM 00.00
(ES:60=1.00)
SELECTION SPEED
SELECTION ENABLE POST-HEATING\COOLING
R/W
LIKE PREVIOUS
R/W
LIKE PREVIOUS
R/W
LIKE PREVIOUS
R/W
LIKE PREVIOUS
R/W
LIKE PREVIOUS
R/W
LIKE PREVIOUS
Manual
26