Series 909/909RPDA
Reduced Pressure Zone Assemblies
Reduced Pressure Detector Assemblies
1
Sizes: 2
" – 10" (65 – 250mm)
2
• Installation
• Service
• Repair Kits • Maintenance
For field testing procedure, send for IS-TK-DL,
IS-TK-9A, IS-TK-99E and IS-TK-99D.
For other repair kits and service parts, send for PL-RP-BPD.
For technical assistance, contact your local Watts representa-
tive on back page.
IMPORTANT: Inquire with governing authorities for local installa-
tion requirements.
NOTE: For Australia and New Zealand, line strainers should be
installed between the upstream shutoff valve and the inlet of the
backflow preventer.
Its important that this device be tested periodically in compliance
with local codes, but at least once per year or more as service
conditions warrant. If installed on a fire sprinkler system, all
mechanical checks, such as alarm checks and backflow preven-
ters, should be flow tested and inspected internally in accor-
dance with NFPA 13 and NFPA 25.
Limited Warranty: Watts Regulator Co. (the "Company") warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES,
EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from
labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control.
This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Watts 909 OSY shown
Designed for inline servicing
RP/IS-909/909RPDA

Advertisement

loading

Summary of Contents for Watts 909Series

  • Page 1 NFPA 13 and NFPA 25. Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
  • Page 2: Basic Installation Instructions

    4. Normal discharge and nuisance spitting are accommodated by the use of a Watts air gap fitting and a fabricated indirect waste 10.START UP at Initial Installation and After Servicing: The down- line. Floor drains of the same size MUST be provided in case of stream shutoff should be closed.
  • Page 3 This is necessary to avoid water hammer or shock damage. G. The installation of a Watts air gap with the drain line termi- nating above a floor drain will handle any normal discharge or nuisance spitting through the relief valve.
  • Page 4 The following procedure is not a specific recommendation. The Watts series of test kits are capable of performing any of the recog- nized backflow test procedures. A. Open TC #4 and flush test cocks Nos. 1, 2, and 3 on BF assembly, then close TC #4.
  • Page 5: Ordering Code

    Servicing First and Second Checks 1. Remove the hatch cover bolts. NOTE: The 909 is designed so that when the bolts are backed off ⁄ ", all the spring load is released from the cover and retained by the check module. Sizes: 2 ⁄...
  • Page 6 Servicing the Relief Valve Sizes: 2 ⁄ " – 10" (65-250mm) 1. Remove the relief valve cover bolts. Note the 909 is designed so Relief Module that when the bolts are backed off ⁄ " all the relief valve spring load is retained by the bottom plug spring module.
  • Page 7 Use Watts No. 15 to eliminate water ham- mer. Replace defective second check assembly. In case of freezing; thaw, disassemble and inspect internal components.
  • Page 8 For additional information, visit our web site at: www.watts.com A Watts Water Technologies Company USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca RP/IS-909/909RPDA 0829 EDP# 1915172 © 2009 Watts...