RET 54_
92
Transformer Terminal
Technical Reference Manual, General
Table 5.2.1-4
RTD/analog inputs
Supported RTD sensors
Max lead resistance
(three-wire measurement)
Accuracy
Isolation
Sampling frequency
Response time
RTD / Resistance sensing
current
Current input impedance
Table 5.2.1-5
Signal outputs
Max system voltage
Continuous carry
Make and carry for 0.5 s
Make and carry for 3 s
Breaking capacity when control circuit time-
constant L/R <40 ms, at 48/110/220 V DC
Table 5.2.1-6
Power outputs
Max system voltage
Continuous carry
Make and carry for 0.5 s
Make and carry for 3 s
Breaking capacity when control circuit time
constant L/R <40 ms, at 48 V DC
110 V DC
220 V DC
Minimum contact load
TCS (Trip Circuit
Control voltage range
Supervision)
Current drain through
the supervision circuit
Minimum voltage
(threshold) over a
contact
1) two contacts in series
Table 5.2.1-7
Analog outputs
Output range
0...20 mA
0.5% of full scale
Accuracy
600
Max load
Isolation
2 kV (output to output, output to inputs and output to protective earth)
Response time
85 ms
100 Platinum
TCR 0.00385 (DIN 43760)
250 Platinum
TCR 0.00385
1000 Platinum
TCR 0.00385
100 Nickel
TCR 0.00618 (DIN 43760)
120 Nickel
TCR 0.00618
250 Nickel
TCR 0.00618
1000 Nickel
TCR 0.00618
10 Copper
TCR 0.00427
120 Nickel
TCR 0.00672 (MIL-T-24388C)
200 per lead
0.5% of full scale
1.0% of full scale for 10 Copper RTD
2 kV (inputs to outputs and inputs to protective earth)
5 Hz
Filter time + 30 ms (430 ms...5.03 s)
max 4.2 mA RMS
6.2 mA RMS for 10 Copper
274 0.1%
250 V AC/DC
5 A
10 A
8 A
1 A/0.25 A/0.15 A
250 V AC/DC
5 A
30 A
15 A
1)
5A
1)
3A
1)
1A
100 mA, 24 V AC/DC (2.4 VA)
20...265 V AC/DC
approx. 1.5 mA (0.99...1.72 mA)
20 V AC/DC (15...20 V)
1MRS755225