Hoffman Controls 890-DSQ Series Complete Installation & Operating Instructions page 17

Based universal sequencer
Hide thumbs Also See for 890-DSQ Series:
Table of Contents

Advertisement

REGISTER
NUMBER
41
Stage 10, Primary set point's On Temp (°F), PSI or Volts DC (All values times 10)
42
Stage 11, Primary set point's On Temp (°F), PSI or Volts DC (All values times 10)
43
Stage 12, Primary set point's On Temp (°F), PSI or Volts DC (All values times 10)
44
Stage 1, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
45
Stage 2, Primary set point's Off Temp °F), PSI or Volts DC (All values times 10)
46
Stage 3, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
47
Stage 4, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
48
Stage 5, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
49
Stage 6, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
50
Stage 7, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
51
Stage 8, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
52
Stage 9, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
53
Stage 10, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
54
Stage 11, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
55
Stage 12, Primary set point's Off Temp (°F), PSI or Volts DC (All values times 10)
56
Stage's On Delay (Since Previous Stage Turned On) in Seconds (All values times 10)
57
Modbus Address (Range 1 - 247)
58
Number of Fixed Stages That Are On (Range 0 - 12)
59
0-5 VDC Input #1 Value (Temperature [°F], Pressure [PSI] or Volts [DC] (All values times 10)
60
0-5 VDC Input #2 Value (Temperature [°F], Pressure [PSI] or Volts [DC] (All values times 10)
61
0-5 VDC Input #3 Value (Temperature [°F], Pressure [PSI] or Volts [DC] (All values times 10)
62
0-5 VDC Input #4 Value (Temperature [°F], Pressure [PSI] or Volts [DC] (All values times 10)
63
0-5 VDC Input #5 Value (Temperature [°F], Pressure [PSI] or Volts [DC] (All values times 10)
64
0-5 VDC Input #6 Value (Temperature [°F], Pressure [PSI] or Volts [DC] (All values times 10)
65
To use secondary set points, 2ND terminal is grounded. (0 = not used, 1 = selected)
66
0-10 VDC Input Value are times 10, and rounded to nearest 0.1 VDC.
67
PWM Output Signal Value is in percent (Range 0% to 100%)
68
Relay sequencing mode (0 = FILO, 1 = FIFO, 2 = Binary Encode)
69
Pressure transducer scale (0 is temp sensor, 1 is 100 PSI, 2 is 200 PSI up to 10 is 1000 PSI.)
Modbus baud rate code (0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19,200; 5 = 38,400;
70
6 = 57,600 and 7 = 115,200)
71
Modbus parity code (38 is even, 54 is odd and 14 is no parity with 2 stop bits)
72
If true (non-zero), reset sequencer to factory settings.
73
High speed output (Range 0 to 100) PWM duty cycle or 0-10 VDC (100 is 10.0 VDC)
74
Low speed output (Range 0 to 100). A low speed output greater than high speed output
means as the voltage goes up, the speed goes down. (See 10 - 0 VDC Output section, page 9)
75
Output for motor off (Range 0 to 100). Example: 5 means PWM is 5% and VDC = 0.5
VDC
16 BIT REGISTER FUNCTION
MODBUS
MODBUS Registers for the 890-DSQ Sequencer
TABLE 2B
17
REGISTER
TYPE
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read & Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read & Write
Read & Write
Read & Write
Read & Write
Write Only
Read & Write
Read & Write
Read & Write