Wireless monitor module

Advertisement

FIGURE 3. BATTERY COMPARTMENT:
BATTERY
COMPARTMENT
MOUNTING
The W-MMF mounts directly to an SMB500 electrical box (see Figure 4). To avoid
interference with the wireless network metal electrical boxes are NOT recommended.
Non-metal surface mounted electrical boxes (SMB500) are available from Fire-Lite.
If not using an SMB500, the minimum mounting opening dimensions for the W-
MMF are 4 in. X 3¾ in. x 1½ in. deep.
NOTE: Do not attach the module to temporary structures such that the placement
could be altered.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and regula-
tions. This module is intended for power limited wiring only. FW-MM must be within
3 feet of monitored device when using field wiring or 20 feet in non-metallic conduit.
1.
Install module wiring in accor-
dance with the job drawings and
appropriate wiring diagrams.
2.
Set the address on the module per
job drawings.
3.
Secure module to electrical box
(supplied by installer), as shown
in Figure 3.
Use of these products in combination with non-Honeywell products in a wireless mesh network, or
to access, monitor or control devices in a wireless mesh nework via the internet or another external
wide area network, may require a separate license from Sipco, LLC. For more information, contact
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment.
This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s). IFT: RCPHOSW14-1983
FL-450-000
September 8, 2015
BATTERY
COMPARTMENT
DOOR
FIGURE 5. TYPICAL MONITORING CONFIGURATION:
ONLY ONE UL LISTED CONTACT
CLOSURE MAY BE USED
3.9K EOL
RESISTOR
A2143-10
INSTITUTO FEDERAL DE TELECOMUNICACIONES
FIGURE 4. MODULE MOUNTING:
C2002-00
POWER LIMITED
3.1 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
W-MMF MUST BE WITHIN 3 FEET OF MONITORED DEVICE WHEN
USING FIELD WIRING OR 20 FEET IN NON-METALLIC CONDUIT.