Appendix - Siemens SGIM-3268H Manual

Vacuum, 5kv and 15kv, type gmi
Table of Contents

Advertisement

Table A-1A – Type GMI Circuit Breaker Ratings (Historic "Constant MVA" Rating Basis)
These ratings are in accordance with the following standards:
ANSI C37.04-1979
Standard Rating Structure for AC High-Voltage Circuit Breaker Rated on a Symmetrical Current Basis
ANSI C37.06-1987
AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis—Preferred Ratings and
Related Required Capabilities
ANSI C37.09-1979
Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
ANSI C37.010-1979
Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
Nominal Voltage Class
General
Nominal 3-Phase MVA Class
Rated
Voltage
Insulation
Levels
Rated
Values
Rated
Current
Current
Related
Required
Capabilities
Closing and
Latching
(Momentary) Peak (2.7 x K x 1)
Footnotes:
1
High close and latch (momentary) rating available for special application.
2
Maximum voltage for which the circuit breaker is designed, and the upper limit for operation.
3
K is the ratio of the rated maximum design voltage to the lower limit of the range of operating voltage in which the required
symmetrical and asymmetrical interrupting capabilities vary in inverse proportion to the operating voltage.
4
3000A ratings with VS-10028 vacuum interrupter are self cooled for indoor installations. 3000A ratings using VA-15050
vacuum interrupter and sperate phase barriers require supplemental fan-cooling in the switchgear circuit breaker structure.
3000A ratings using VS-15050 vacuum interrupter and chair design support are self-cooled for indoor installations. Consult
drawings for the switchgear for arrangement provided.
5
To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated
maximum design voltage and rated maximum design voltage, the following formula shall be used: Required Symmetrical
Interrupting Capability = Rated Short-Circuit Current (I) x [(Rated Maximum Design Voltage) / (Operating Voltage)] For
operating voltages below 1/K times rated maximum design voltage, the required symmetrical interrupting capability of the
circuit breaker shall be equal to K times rated short-circuit current.
6
Within the limitations stated in ANSI C37.04-1979, all values apply to polyphase and line-to-line faults. For single phase-to-
ground faults, the specific conditions stated in clause 5.10.2.3 of ANSI C37.04-1979 apply.
7
Current values in this row are not to be exceeded even for operating voltage below 1/K times rated maximum design voltage
For operating voltages between rated maximum design voltage and 1/K times rated maximum design voltage, follow footnote
5 above.
8
Current values in this row are independent of operating voltage up to and including rated maximum design voltage.
9
"Nominal 3-Phase MVA Class" is included for reference only — this information is not listed in ANSI C37.06-1987.
10
Standard duty cycle is CO – 15s – CO
Courtesy of NationalSwitchgear.com
Measured Parameter
9
Maximum Design Voltage (V)
Voltage Range Factor (K)
3
Power
Frequency
Withstand
Voltage Levels
Lightning
Impulse (BIL)
Continuous
4
Short-Circuit (at rated maximum
design voltage) (I)
5 6 10
Interrupting Time
Permissible Tripping Delay (Y)
Rated Maximum Design Voltage
(V) divided by K (= V/K)
Max. Sym Interrupting (K x 1)
Short Time Current (K x 1)
(3 seconds)
Asymmetrical (1.6 x K x 1)
8
8
Units
5-GMI-
5-GMI-
250
350
kV
4.16
4.16
MVA
250
350
2
kV rms
4.76
4.76
1.24
1.19
kV rms
19
19
kV crest
60
60
1200
1200
A rms
2000
2000
3000FC 3000FC
kA rms
29
41
sym
Cycles
5
5
Sec.
2
2
KV rms
3.85
4.0
kA rms
7
36
49
sym
kA rms
36
49
58
kA rms
78
78 opt
1
97
kA peak
132
132 opt
1

Appendix

Circuit Breaker Type
7-GMI-
15-GMI- 15-GMI- 15-GMI-
500
500
750
7.2
13.8
13.8
500
500
750
8.25
15.0
15.0
1.25
1.30
1.30
36
36
36
95
95
95
1200
1200
1200
2000
2000
2000
3000FC 3000FC
33
18
28
5
5
5
2
2
2
6.6
11.5
11.5
41
23
36
41
23
36
66
37
58
77 opt
1
58 opt
1
77 opt
1
111
62
97
130 opt
1
97 opt
1
130 opt
1
1000
13.8
1000
15.0
1.30
36
95
1200
2000
37
5
2
11.5
48
48
77
130
47