Table of Contents Typical applications of UK24LON unit UK24LON unit data sheet UK24LON unit dimensions Complete MFT(2)/MP assortment Connecting MFT(2)/MP actuators Connecting sensors MP-Bus conductor lengths Functional Profile 8–9 ® SNVT functions of the function objects Operation, Characteristics 12–13 Connecting MFT parameterising tools...
MFT(2)/MP- push-screw terminals, 4-pole Parameterising MFT(2)/MP actuators actuators: (all terminals for 1,5 mm Using the Belimo PC-Tool it is very easy to MFT-H: plug socket, 3-pole preset specific parameters (e.g. running or MFT parameterising tools) time) for individual actuators. An MFT pa-...
UK24LON unit dimensions, connectable actuators UK24LON unit dimensions Complete MFT(2)/MP assortment for connection to the UK24LON Damper actuators with or without safety function MP-VAV devices Actuators for characterised control ball valves with or without spring- return function Actuators for globe valves with or...
(e.g. Pt1000, contact. This provides a simple means can be passed on to L via the ® ORKS UK24LON unit. ® ORKS Note: ... MFT = Active sensors and switches can be connected ... MFT2/MP = Active sensors, switches and passive...
0.75 lengths to be substantially greater. Regardless of the power ratings of the actuators connected to the UK24LON unit the conductor lengths are then as stated in the adjacent table.
UK24LON unit, Functional Profile ® ARK ® Functional Profile The UK24LON unit can link a maximum of 8 MFT(2)/MP actuators with an MP-Bus capability to L ORKS ® . The UK24LON Gateway converts the digital communications processes of the MP-Bus to standard L ARK ®...
Page 9
UK24LON unit, Functional Profile ® Functional Profile for 8 MFT(2)/MP damper actuators and 8 sensors implemented in a UK24LON unit UK24LON Damper Actuator Object #8110 Damper Actuator Object #8110 Damper Actuator Object #8110 Damper Actuator Object #8110 nviRelStpt nvoActualValue nviRelStpt...
SNVT functions of the function objects Explanation of SNVT functions of the function objects An MFT(2)/MP damper actuator or characterised control valve actuator is connected to the UK24LON: nviRelStpt: Setpoint for actuator Damper Actuator Object #8110 position (0...100% angle of rotation).
Page 11
Explanation of SNVT functions of the function objects A VAV-MP device is connected to the UK24LON: nviRelStpt: Setpoint for VAV Damper Actuator Object #8110 controller of the VAV unit (0...100% nominal volumetric flow of the VAV nviRelStpt nvoActualValue unit). SNVT_lev_percent...
S2 button). must be connected first. table stored in the UK24LON unit. If an ac- The UK24LON unit will then be able to Press the Up button to select the ●...
A flashing LED Error and simultaneous UK24LON unit will be deleted. It will be not been registered or are incorrect. display of the MP addresses indicates a registered again when the actuator is mechanical fault of the corresponding reconnected.
Page 16
On site around the globe A complete range of products from one source Tested quality Short delivery times Comprehensive support Headquarters Subsidiaries, Representatives and Agencies BELIMO Holding AG Argentina Denmark Lebanon Rumania Brunnenbachstrasse 1 Australia Egypt Liechtenstein Russia CH-8340 Hinwil Austria...
Need help?
Do you have a question about the UK24LON and is the answer not in the manual?
Questions and answers