Technical information
© 08.2020 Lindab Ventilation. All forms of reproduction without written permission are forbidden.
Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
Controller
®
l i n da b | w e s i m pl i fy co n s t r u c t i o n
is the registered trademark of Lindab AB.

Advertisement

Table of Contents
loading

Summary of Contents for Lindab UltraLink FTCU

  • Page 1 LindabUltraLink ® FTCU Technical information © 08.2020 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
  • Page 2: Table Of Contents

    This offers great advantages for the user in terms of comfort and savings in energy consumption, which is of great interest. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 3: Overview

    IP42 Lindab UltraLink Controller FTCU CE-mark Bluetooth ® IP classification logotype Status light Display parameters Lindab reserves the right to make changes without prior notice Lindab reserves the right to make changes without prior notice 2020-08-05 2020-08-05...
  • Page 4: Mounting

    If the damper needs to be turned manually, then press the manual override button button on the motor and turn the damper shaft with a 8 mm wrench or similar. Damper shaft Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 5 19. Disturbance Placement of first flow sensor 2-4·Ød >4-5·Ød >5·Ød Inner radius Bend 90° (Best position) Ød Outer radius Bend 90° (Not recommended) Ød Ød Bend 90° Side Ød Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 6 Placement of first flow sensor Duct diameter Reducer Ød decrease Duct diameter Reducer Ød increase Inner radius T-piece (Best position) Ød Outer radius T-piece (Not recom- mended) Ød Ød T-piece Side Ød Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 7: Electrical Installation

    FTCU. • In case electrical installation equipment such as a junction box is needed for installation, the FTES is a Lindab accessory which can be mounted on the FTCU without causing damage to the FTCU. •...
  • Page 8 RTU and the analog in signal (AIN) is connected to the analog out terminal on the RTU. Also make sure to connect the cables to the same analog ground. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 9 If the bus is longer than 300 meters or if there are more than 30 devices, the system might need an RS485 repeater (FDS-R, see picture to the right) to be able to communicate in an efficient way. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 10 The power consumption for dimensioning supply cables for an UltraLink FTCU is 3-5 VA. See details on page 19. ® It is not recommended to use a transformer with a higher capacity than 150 VA. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 11: Commissioning

    If the UltraLink is equipped with Bluetooth (the Bluetooth logotype is printed on the display unit), wireless communication with the UltraLink can be established. Using a smartphone with the Lindab UltraLink app, nearby UltraLinks will be identified. Now you can connect to all the different UltraLink units to change settings and view information regarding each UltraLink.
  • Page 12 Flashing light every 3 second Bluetooth is on stand by and is ready to connect to mobile device. Flashing light every 1 second A mobile device has been connected to the FTCU. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 13 • connect a Bluetooth device and use the “UltraLink” application. Maintenance The FTCU does not normally require any maintenance. The visible parts of the device can be wiped with a damp cloth. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 14 After that you short press to toggle to the desired number, then you long press to move the blinking cursor to the next single number in the current value. Proceed until the new value has been set and long press to continue. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 15: Digital Communication Settings

    Modbus, but preferably the UltraLink® Con- figuration tool (See separate documentation). For more register details see appendix. Lindab reserves the right to make changes without prior notice Lindab reserves the right to make changes without prior notice...
  • Page 16: Analog Communication Settings

    *) 0% means fully closed damper position and 100% means fully open damper position. PLEASE LOOK IN THE APPENDED MODBUS REGISTER FOR INSTRUCTIONS ON HOW TO CHANGE REGISTER VALUES. SOME VALUES HAS SCALE FACTORS AND SOME VALUES OCCUPY TWO REGISTERS! Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 17 *) 0% means fully closed damper position and 100% means fully open damper position. PLEASE LOOK IN THE APPENDED MODBUS REGISTER FOR INSTRUCTIONS ON HOW TO CHANGE REGISTER VALUES. SOME VALUES HAS SCALE FACTORS AND SOME VALUES OCCUPY TWO REGISTERS! Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 18: Troubleshooting

    • the flow sensors are not connected properly into the display unit • the sensor body is flawed Err032 Factory data is corrupted Reset to factory defaults using UltraLink configuration tool ® Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 19: Technical Data

    Screws on lid of display unit Philips (PH1) 4 pcs Bluetooth radio Frequency 2402 — 2480 MHz Output power -40 to +9 dB Lindab reserves the right to make changes without prior notice Lindab reserves the right to make changes without prior notice 2020-08-05 2020-08-05...
  • Page 20: Appendix A - Modbus Register

    3x150 Velocity in m/s Velocity in m/s Float 3x152 Air flow in m³/h Air flow in m³/h Float m³/h 3x154 Air flow in l/s Air flow in l/s Float Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 21 Configure TX Power Level dBm. Accepted 16bit values: -40, -20, -16, -12, -8, -4, 0, 2, 3, 4, 5, 6, 7, 8, 9 * = the value depends on the dimension of the product. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 22 Max open % shown = Max output voltage 16bit 1000 1000 Max. (Only relevant when 4x401 is set to 2 ) * = the value depends on the dimension of the product. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 23 Highest voltage level to activate 1st Override 16bit Trigger Max. level (Only relevant when 4x500 is set to 2 or 3) * = the value depends on the dimension of the product. Lindab reserves the right to make changes without prior notice 2020-08-05...
  • Page 24 At Lindab, good thinking is a philosophy that gui- des us in everything we do. We have made it our mission to create a healthy indoor climate – and to simplify the construction of sustainable buil- dings. We do that by designing innovative pro- ducts and solutions that are easy to use, as well as offering efficient availability and logistics.