Potterton Derwent Compact Plus Installation, Operation & Maintenance Manual page 5

Table of Contents

Advertisement

POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
DERWENT COMPACT PLUS – CONDENSING
Fig- 2 – Steel Base Strip Details – (see section 2 – Boiler Siting and Base)
485
710
The boiler feet MUST NEVER be fixed in position (this is to allow for expansion).
Sections
4
G mm
171
CLEARANCES
The minimum boiler room clearances for access, erection and maintenance are as follows: -
REAR -
500mm from rear of flue hood
SIDES -
10mm
FRONT -
700mm (to allow for burner removal)
TOP
-
1000mm (to allow for cleaning)
Flammable products should never be stored in the space around the boiler. Any walls that are sensitive to heat
should be protected by an appropriate insulation.
6
8
324
486
G
Centre Line
Of Boiler
FRONT OF BOILER
SECTION 1
PAGE 3