Philips Compac CTX6 Series Quick Manual page 2

Commercial thermoplastic emergency unit with xtest

Advertisement

CM-22200
Xtest
testing specifications
• Automatic Test: The system charger and lamps are continually being
controlled via pre-determined parameters specific to each model
configuration, automatically. The battery is controlled via a true open circuit
test each hour after initial installation. One each month the
illuminates lamps under load for 30 minutes, simulating a power outage
with a true charger off condition, without affecting long term battery life.
This is above and beyond the requirements of the National Fire Protection
Association. This gives you unequaled control and confidence, knowing you
are meeting self-test code requirements each and every month.
Fault Indications:
Four LED indicators provide visible indication of system status:
AC/Green
Charger/Red
Batt/Red
On
F
On
F
On
F
On
On
On=Steady
F=Flashing
dimensions
11-1/16"
(280.9mm)
© 2016 Philips Lighting Holding B.V. All rights reserved.
Philips reserves the right-make changes in specifications
and/or-discontinue any product at any time without notice
or obligation and will not be liable for any consequences
resulting from the use of this publication.
philips.com/luminaires
CM-22200 08/16 page 2 of 2
CTX6 Series Compac
Xtest
System
Lamp/Red
F
F
Lamp/Battery Disconnected or Charger Fault
F
Battery disconnected/fault
F
Lamp disconnected/bad or remote disconnected
Blank=Off
5-11/16"
(128.3mm)
5-1/4"
(133.6mm)
Thermoplastic Emergency Unit with
®
• Manual Test: A manual test switch allows for the
the following tests at any time:
Press Button
Once–5 second test, charger off, no load
Twice–60 second test, charger off, lamps on
Three–90 minute test, charger off, lamps on
6-Second Hold–Fully reinitializes micro-processor.
Pressing once during any test will cancel/abort testing.
Xtest
Status Indicator Panel
SELF-TEST / DIAGNOSTIC
CHG-TEST
Location of sensor for laser activation
of manual test via handheld remote laser
tester (this is an optional feature, specify
"LX" option)
Status/Fault
AC power is on/OK
Performing Test
Charger fault
*If unit has remote capacity and remote cable is connected to charger board but not connected to
a remote load, then either connect remote load or disconnect cable from charger board.
photometry
CTX6
CTX618 9W tungsten
Meets Life Safety Code standard minimum illuminance of 0.1 FC and average
illuminance of 1.0 FC. Assumes open space with no obstructions, mounting
height: 8', ceiling height: 9', and reflectances: 80/50/20. Analysis based on
independently tested photometrics.
Test Numbers:
CTX6 - CSWA
CTX618 - CSWC
Philips Lighting North America Corporation
200 Franklin Square Drive, Somerset, NJ 08873
Tel. 855-486-2216
Philips Lighting Canada Ltd.
281 Hillmount Rd, Markham, ON, Canada L6C 2S3
Tel. 800-668-9008
Xtest
CHARGER
BATTERY
LAMPS
Action
None
None
Check connections; if ok, replace circuit board
Replace circuit board
Check connection or replace battery
Check connection then press manual test once to
determine bad lamp/replace lamp or check remote lamp.*
lamp
spacing
avg. fc.
max. fc.
5.4W tungsten
24ft.
1.0
2.00
39ft.
1.4
2.70
Xtest
system to perform
3'
min. fc.
0.1
0.1