Calibration

Every TSTAT0713 is calibrated before it leaves the factory.
:
8 00
78
74
Am
o
M
o
COOL
AUTO
70
HEAT
o
Under normal circumstances there will never be a need to recalibrate
the TSTAT0713 again.
To accommodate special needs, the thermostat may be recalibrated
following these steps:
1. While pressing the MODE button, press the FAN button for
5 seconds. After all the icons in the display appear, release
the buttons.
2. Press the UP & DOWN buttons at the same time; the display will
change.
3. Press the UP & DOWN buttons at the same time again; the current room
temperature will be displayed.
4. Use an accurate thermometer to measure room temperature. Press the
UP or DOWN buttons until the displayed temperature equals the room
temperature.
5. Press the MODE button; the current humidity will be displayed.
6. Use an accurate hygrometer to measure room humidity. Press the UP or
DOWN buttons until the displayed humidity equals the room humidity.
7. Press the mode button to return to normal operation.
Page 14