Static Checkout; Equipment Recommended; General Instructions - Honeywell 7800 Series Installation Instructions Manual

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

STATIC CHECKOUT

After checking all wiring, perform this checkout before install-
ing the EC7895A,C/RM7895A,B,C,D/RM7896A,B,C,D on
the subbase. These tests verify the Q7800 Wiring Subbase is
wired correctly, and the external controllers, limits, interlocks,
actuators, valves, transformers, motors and other devices are
operating properly.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury, or death.
Close all manual fuel shutoff valve(s) before starting
these tests.
Use extreme care while testing the system. Line voltage
is present on most terminal connections when power is
on.
Ensure proper selection of configuration jumpers before
starting the burner operation.
CAUTION
Electrical Hazard.
Can cause equipment damage or failure.
Do not perform a dielectric test with the relay module
installed. Internal surge protectors can break down,
allowing relay module to fail the dielectric test and
destroy the internal lightning and high current
protection.
1. Open the master switch before installing or removing a
jumper on the subbase.
2. Before continuing to the next test, be sure to remove the
test jumper(s) used in the previous test.
3. Replace all limits and interlocks that are not operating
properly. Do not bypass limits and interlocks.
Test
Relay
Number
Module
Model
1
All
None
2
All
None
3
All
4-5
4
All
5-10
Table 6. Static Checkout.
Test
Voltmeter
Jumpers
5-L2
6-L2
7-L2
RM7895A,B,C,D/EC7895A,C; RM7896A,C,D7800 SERIES Relay Modules

Equipment Recommended

1. Voltmeter (1M ohm/volt minimum sensitivity) set on the 0
to 300 Vac scale.
2. Two jumper wires, no. 14 wire, insulated, 12 in. (304.8 mm)
long with insulated alligator clips at both ends.

General Instructions

1. Perform all applicable tests listed in Static Checkout, Table
6, in the order listed.
2. Make sure all manual fuel shutoff valve(s) are closed.
3. For each test, open the master switch and install the jump-
er wire(s) between the subbase wiring terminals listed in
the Test Jumpers column.
4. Close the master switch before observing operation.
5. Read the voltage between the subbase wiring terminals
listed in the Voltmeter column.
6. If there is no voltage or the operation is abnormal, check
the circuits and external devices as described in the last
column.
7. Check all wiring for correct connections, tight terminal
screws, correct wire, and proper wiring techniques. Re-
place all damaged or incorrectly sized wires.
8. Replace faulty controllers, limits, interlocks, actuators,
valves, transformers, motors and other devices, as re-
quired.
9. Make sure normal operation is obtained for each required
test before continuing the checkout.
10. After completing each test, be sure to open the master
power switch and remove the test jumper(s) before pro-
ceeding to the next test.
WARNING
Explosion hazard.
Can cause serious injury or death.
Be sure all manual fuel shutoff valves are closed.
Normal Operation
Line voltage at terminal 5.
Line voltage at terminal 6.
1. Burner motor (fan or blower)
starts.
2. Line voltage at terminal 7 within
10 seconds.
1. Ignition spark (if ignition
transformer is connected to
terminal 10).
9
If Operation is Abnormal,
Check Items Listed Below
1. Master switch.
2. Power connected to master
switch.
3. Overload protection (fuse,
circuit breaker, etc.) has not
opened power line.
1. Limits.
2. Burner controller.
1. Burner motor circuit.
a. Manual switch of burner motor.
b. Burner motor power supply,
overload protection and starter.
c. Burner motor.
1. Watch for spark or listen for
buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
32-00156-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents