DESCRIPTION
The Model 95DISP-1 and 95DISP-1-SS are two-line by sixteen-character alpha-numeric Vacuum-
Fluorescent Displays (VFD) with a five-pushbutton keypad. The 95DISP-1 is installed by the user
onto the end of the standard scanners. The 95DISP-1-SS is factory installed into the 95DSS3-
1CEXSS and 95DSS3-1CEX-2 scanners.
The Model 95WIDISP-2 is an Infrared Transmitter Module with four LED indicators for use with the
95DSS3 InSight II flame scanner. Once installed, the user then programs the 95DSS3 via a remote
95WIHH-2 Wireless Handheld Commissioning Tool, ordered separately. Refer to bulletin 133-735
for additional details.
The Model 61-7347-1 Blank Cover must be installed to maintain environmental ratings when neither
the 95DISP-1 nor 95WIDISP-2 is installed. With the 61-7347-1 Blank Cover installed, operator
interface must either be via "Fireye Explorer" pc software, or by temporarily installing a 95DISP-1 or
95WIDISP-2.
The 95DSS3 InSight II flame scanner requires either the 95DISP-1 Display, the 95DISP-1-SS dis-
play, the 95WIDISP-2 Transmitter, or the 61-7347-1 Blank Cover. Refer to bulletin CU-113 for
detailed description of the 95DSS3 scanner.
INSTALLATION INSTRUCTIONS
The following are the steps required to install the 95DISP-1 Display, 95WIDISP-2 Transmitter, or
61-7347-1 Blank Cover into a new 95DSS3 InSight II scanner. If you are replacing a 95DSS3 scan-
ner's damaged unit, you must first remove power from the scanner and move it to a clean, dry, non-
hazardous area.
95WIDISP-2
95WIDISP-2 IR TRANSMITTER
1. Remove the threaded Locking
Ring from the 95DSS3
scanner.
2. Remove the plastic end cap.
3. Verify that the scanner housing
o-ring is properly seated in the
95DSS3 scanner.
®
95DISP-1 DISPLAY,
95DISP-1-SS DISPLAY,
and 61-7347-1 BLANK COVER
For use with 95DSS3
CU-116
OCTOBER 13, 2015
1

Advertisement

loading

Summary of Contents for Fireye 95DISP-1

  • Page 1 The Model 61-7347-1 Blank Cover must be installed to maintain environmental ratings when neither the 95DISP-1 nor 95WIDISP-2 is installed. With the 61-7347-1 Blank Cover installed, operator interface must either be via "Fireye Explorer" pc software, or by temporarily installing a 95DISP-1 or 95WIDISP-2.
  • Page 2 95DSS3. 2. Position the 95DISP-1 Display in the 95DSS3, making sure that the notch in the rear of the 95DISP-1 aligns with the key in the 95DSS3 housing. 3. Install the second o-ring into the machined groove on the outside of the 95DISP-1 (not shown) 4.
  • Page 3 The locking Ring must be very firmly torqued for the seal to be effective. A strap wrench or similar tool with a 12 inch minimum handle is recommended rather than installation only by hand 95DISP-1 Installed 61-7347-1 Installed 95WIDISP-2 Installed...
  • Page 4 Fireye warranty, as stated it its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance.

This manual is also suitable for:

95disp-1-ss95widisp-261-7347-1