Page 1
PSBS 10A12E v.1.0 PSBS 13,8V/10A/65Ah Buffer, switched mode power supply unit. Edition: 3 from 16.09.2013 Supersedes the edition: 2 from 18.09.2012...
- PSBS 10A12E + 2xRN500 (13,8V/12V) + 65Ah 6. Buffer power supply unit PSBS 13,8V/2x12V/16x0,5A/65Ah - PSBS 10A12E + 2xRN500 (13,8V/12V) + 2xLB8 16x0,5A (AWZ578 or AWZ580) + 65Ah 7. Buffer power supply unit PSBS 13,8V/2x12V/10x1A/65Ah - PSBS 10A12E + 2xRN500 (13,8V/12V) + 2xLB8 10x1A (AWZ579 or AWZ580) + 65Ah 8.
Page 4
PSBS10A12E Ibat =2,1A Ibat =3,6A Ibat =4,8A Caption: jumper on, jumper off +BAT - DC supply battery output [11] (+BAT= red, -BAT = black) FAC - AC absence technical output –OC type (open collector) [12] hi-Z level = status: AC power failure L level = status: AC supply FPS - technical output of the PSU operation status –...
Page 5
PSBS10A12E Table 2. Element no. Description [Fig. 3] Insolation transformer PSU board (tab. 1) TAMPER micro-switch (contacts) of tamper resistance (NC) fuse in the supply circuit (230 V AC) MAIN L-N 230 V AC power connector PE – PE connector Battery connectors: +BAT = red, - BAT = black Tab 2.
PSBS10A12E Operation safety (tab.5). Protection class PN-EN 60950-1:2007 I (first) Protection grade PN-EN 60529: 2002 (U) IP20 Electrical strength of insulation: - between input (network) circuit and output circuits of the PSU (I/P-O/P) 3000 V/AC min. - between input circuit and PE protection circuit (I/P-FG) 1500 V/AC min.
PSBS10A12E - FAC; AC status indication (alarm panel, controller, indicator, LED, etc.) - FPS; technical output of the PSU operating status. - TAMPER; indication of unwanted enclosure opening or detachment from the mounting surface. 6. With the I (J1, J2) jumpers determine the maximum battery charging current, in accordance with the battery parameters (see tab.1)
PSBS10A12E 4. Operation and use. 4.1 Overload or short circuit of the PSU output The output circuit of the PSU is equipped with the electronic current protection. If the output voltage value exceeds the acceptable threshold – Imax, the PSU output will be disconnected. The disconnection will be indicated by the O1, O2, O3 and AUX diodes going out.
Page 10
GENERAL WARRANTY CONDITIONS 1. Pulsar K. Bogusz Sp.j. (the manufacturer) grants a five-years warranty for the equipment, counted from the device’s production date. 2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the manufacturer’s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects,...