Cooper Notification E70H Series Installation Instructions

Cooper Notification E70H Series Installation Instructions

High fidelity low-profile speakers

Advertisement

INSTALLATION INSTRUCTIONS
SERIES E70H/E90H HIGH FIDELITY
LOW-PROFILE SPEAKERS
Use this product according to this instruction manual. Please keep this instruc-
tion manual for future reference.

GENERAL

The Wheelock Series E70H/E90H High Fidelity Low Profile Speakers are UL
Listed under UL Standard 1480 for Speaker Appliances and ULC Listed under
Standard CAN/ULC-S541-07 for Speaker Appliances. They are designed for
multiple power requirements with high dBA output at each power tap. All mod-
els offer a choice of field selectable taps, 1/8W to 2W, for either 25.0 V
70.0 V
audio systems. The Low Profile design incorporates a high efficiency
RMS
speaker for maximum output at minimum power across a frequency range
of 300-8000Hz. The Series E70H/90 appliances also incorporate a Speaker
Mounting Plate attached to the speaker for ease of installation. All models
are Listed for indoor use only with the backboxes specified in these instruc-
tions (see wiring and mounting information). 1/8W tap setting for Private
Mode only. E70H/E90H series speakers are UL rated to meet the NFPA 72
requirement for 520Hz signals in sleeping areas when used in conjunction
with Wheelock Safepath products (see SP40S manual for more details)
NOTE: All Canadian Installations should be in accordance with the Canadian
Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524-01 and
Canadian Electrical Code, Part 1. Final acceptance is subject to Authorities
Having Jurisdiction.
WARNING: The speaker appliance is a "fire alarm device - do not paint".
WARNING: Please read these instructions carefully. Failure to comply with
any of the following instructions, cautions and warnings could result in
improper application, installation and/or operation of these products in an
emergency situation, which could result in property damage and serious
injury or death to you and/or others.

SPECIFICATIONS

Table 1A: UL Listed Models and Ratings
Model
Voltage
(V
)
RMS
25/70
E70H
25/70
E90H
Table 1B: ULC Listed Models and Ratings
Model
Anechoic dBA Per
CAN/ULC-S541-07 (Rated Watts)
1/4
E70H
74
77
E90H
73
76
Table 2: ULC Directional Characteristics
25/70V
-3dBA
+/- 19 degrees horizontal; +/- 35 degrees vertical
-6dBA
+/- 40 degrees horizontal; +/- 45 degrees vertical
NOTES
1. Models are Listed for indoor use with a temperature range of +32°F to
+120°F (0°C to +49°C) and maximum humidity of 93% RH. The effect of
shipping and storage temperatures shall not adversely affect the perfor-
mance of the appliance when it is stored in the original cartons and is not
subjected to misuse or abuse.
2. The maximum supervision voltage is 33 volts DC.
3. Frequency range of speakers is 300-8000Hz.
PN P85326B
Speaker
dBA at 10 Feet
(Rated Watts)
1/8
1/4
1/2
1
72
75
78
81
72
75
78
81
Speaker
Mounting
Options
1/2
1
2
80
83
85
79
82
85
Copyright 2015 Cooper Wheelock, Inc. dba Cooper Notification
CAUTION: Always operate audio amplifiers and speakers within their speci-
fied ratings. Excessive input may distort sound quality and may damage
audio equipment. Do not exceed 100% of speaker input voltage per UL 1480.
Improper input voltage can damage speaker. If distortion is heard, check for
clipping of the audio appliance with an oscilloscope and reduce the amplifier
input level or gain level to eliminate any clipping.

WIRING AND MOUNTING INFORMATION

or
CAUTION: The following figures show the maximum number of field wires
RMS
(conductors) that can enter the backbox used with each mounting option. If
these limits are exceeded, there may be insufficient space in the backbox to
accommodate the field wires and stresses from the wires could damage the
product. Check that the installed product will have sufficient clearance and
wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4-inch (1.9-cm) conduit fittings are used.
Although the limits shown for each mounting option comply with the National
Electrical Code (NEC), Cooper Notification recommends use of the largest
backbox option shown and the use of approved stranded field wires, whenever
possible, to provide additional wiring room for easy installation and minimum
stress on the product from wiring.
NOTE: Surface backbox (SBB) in Figure B is compatible with wiremold and
conduit, mounting holes are for single-gang, double-gang, 4-inch (10.16-cm)
sq. (10.16-cm), 3-1/2-inch (8.9-cm) and 4-inch (10.16-cm) octagon or round
backboxes.
A
FLUSH M O UNTING
(NO N-STRO BE SPEAKER)
4" SQ . X 1-1/2"
EXTENSIO N RING *
#8-32
SCREW S
SQ UARE O R
#6-19
RO UND G RILLE
SCREW S
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG#12
4
4
2
83
NOTE: E90H has a round grille. E70H is shown.
82
• This model has in-out wiring terminals that accept two #12 to #18 American
Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches (.96
cm) and connect to screw terminals.
• Break all in-out wire runs on supervised circuits to ensure integrity of circuit
supervision as shown in Figure 1. The polarity shown in the wiring diagrams
is for operation of the appliances.
A,B
A
GROUNDING: Connect ground wire to backbox. Install signaling appliance to
backbox using mounting screws provided
273 Branchport Ave.
Long Branch, N.J. 07740
www.coopernotification.com
SU R FAC E M O U N TIN G
B
(N O N -STR O BE SPEAKER )
SU R FAC E
4" SQ . X 2-1/8"
BAC KBO X
BACKBO X
(SBB)
#8-32
SC R EW S
SPEAKER
M O UNTING
PLA TE
SQ U AR E
G R ILLE
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG#12
4
4
4
Figure 1
(800) 631-2148
SPEAKER
M O U N TIN G
PLATE
#6-19
SC R EW S
4
4
4
Figure 2
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E70H Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cooper Notification E70H Series

  • Page 1 Although the limits shown for each mounting option comply with the National requirement for 520Hz signals in sleeping areas when used in conjunction Electrical Code (NEC), Cooper Notification recommends use of the largest with Wheelock Safepath products (see SP40S manual for more details)
  • Page 2 THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND COOPER NOTIFICATION WILL NOT HAVE ANY LIABILITY FOR SUCH USE. 12/15 PN P85326B Copyright 2015 Cooper Wheelock, Inc.

This manual is also suitable for:

E90h seriesE90h-wE90h-rE70h-wE70h-r

Table of Contents