3.2
Electrical Connection
Complete the mechanical installation before you connect the device electrically.
Set up all electrical connections while the voltage supply is switched off.
Connect power supply to terminals 1 (+) and 2 (-). The casing is electrically connected to
terminal 2.
Set the signaling function via the configuration switch:
0
output triggered when covered with product
1
output triggered when not covered with product
A bi-color LED indicates the system status:
green
device ready
red
output ON
An ON output is available at terminal 3 (high signal). The output is 50 mA max. and is
short-circuit-proof.
3.3
Sensitivity adjustment and delay
Sensitivity and delay can be adjusted either via the configuration DIP switches or alterna-
tively using the optional programming set.
BA_079_2019-05_10.00 Limit switch LIMES
Figure 1: electrical connection
Figure 2: configuration DIP switches
Page 3/5