Download Print this page

APT LW39-25 Series Quick Manual

Advertisement

Quick Links

Cam Switch
Instructions
Before installing the device, please read the instructions.
WARNING
Hazardous voltage
can cause electrical shock and burns
Disconnect power before proceeding
with any work on this equipment
Summary
Main application
LW39-25 switch is also used to control the start, brake,
clockwise and anti-clockwise of small capacity motor
and the speed governing of two-speed motor.
General product information:
Model specification
LW 39 - 25 □ - □ - □
① ②
③ ④
Switch type
Design number
Specification
Function code
Operating characteristics of code
Relative of nodes or section code
Stages
Panel code
Illuminated code
Handle style
Auxiliary code
Installation caution
1) We need to check whether the type meet selection requirement.
2) We must turn off power before installation and recondition.
3) Wiring refer to drawing and turn on the power after you check
carefully.
4) Choose the correct operational voltage and current.
5) To prevent impurities metal powder into the product inside .
6) Tighten all terminal screws even if not used.
7) Don't open the parts with red mark.
Technical feature
Parameters
1) Rated insulation voltage(Ui) : 690 V
2) Conventional thermal current(Ith) : 16 A
3) Power frequency withstand voltage : 1890 V / 5 s
4) Mechanical life : 30 X 10
5) Electrical life : AC / 20 X 10
DC / 10 X 10
6) Type of fuse used in test of rated conditional short-circuit
current:NT00-25A
7)
The ability of terminals wire:
(1) The largest cross-section: 4 mm²; the maximum number
of conductors connected to the terminal : 2
(2) The largest cross-section: 1 mm²; the maximum number
of conductors connected to the terminal: 2
(3) Tightening torque: 1.2 N·m.
8) Usage category
Usage
Ue(V)
24 V
category
Ie(A)
DC-13
-
Ie(A)
AC-15
-
Ie(A)
AC-3
-
Ie(A)
AC-4
-
Ie(A)
AC-21
-
Ie(A)
AC-22
-
Siemens Electrical Apparatus Ltd., Suzhou, Tiantai Branch
Jigong Avenue 699- 10 Tiantai, Zhejiang,China
Sales Dept :Tsidi Building No.55,Lane 777,West Guangzhong Road Shanghai
Tel : 021-56553757
□ / □ - □ - □ - □ - □
···
⑧ ⑨
⑩ ⑪
4
times
4
times
4
times
48 V 110 V
220 V
380 V
-
2.5 A
1.25 A
-
-
-
12 A
8 A
-
-
-
12 A
-
-
-
10 A
-
-
-
25 A
-
-
-
25 A
http://www.china-apt.com
Drawing No. : APT0.463.022.10
Operation condition
1) Environment temperature : -25°C to +55°C
2) Relative air humidity ≤ 90%
3) Altitude ≤ 2000 meters
4) Installation category : Ⅲ
5) Pollution class : 3
The light box schematic diagram
1) Three terminals
[The common is anode]
2) Three terminals
[The common is cathode]
3) Four terminals
[There is no common, Intermediate is cathode]
4) Four terminals
[There is no common, Intermediate is anode]
Note:Be careful to disassemble or assemble
light box , to avoid damaging them.
2017.1
LW39-25
, GB 14048.5
EN60947-5-1
-----default
R
R
R
R
X1
X0
X2
(+)
(-)
(+)
R
R
R
R
X1
X0
X2
(-)
(+)
(-)
R
R
R
R
X1
X0
X0
X2
(+)
(-)
(-)
(+)
R
R
R
R
X1
X0
X0
X2
(-)
(+)
(+)
(-)
3

Advertisement

loading
Need help?

Need help?

Do you have a question about the LW39-25 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for APT LW39-25 Series

  • Page 1 12 A Ie(A) AC-4 10 A Ie(A) AC-21 25 A Ie(A) AC-22 25 A Siemens Electrical Apparatus Ltd., Suzhou, Tiantai Branch Jigong Avenue 699- 10 Tiantai, Zhejiang,China Sales Dept :Tsidi Building No.55,Lane 777,West Guangzhong Road Shanghai Tel : 021-56553757 http://www.china-apt.com 2017.1...
  • Page 2 LW39-25 LW39-25YS Installation L: The size of the switch body t=1~3 t : The thickness of the mounting plate 6xØ4.5 n: The stage of the switch Ø23 LW39-25 t=1~3 30±0.2 4xØ4.5 48±0.2 76±0.5 L= ( 49.5+13.5 x n ) ±2 17±1 29.5±1 Ø10...

This manual is also suitable for:

Lw39-16nxlcLw39-16nxlfLw39-16nxtcLw39-16nxtfLw39-16nxlcdLw39-16nxlfd ... Show all