O-33 Drive Port Parity
Option:
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
O-35 Minimum Response Delay
Range:
10. ms*
[5. - 10000. ms]
O-36 Maximum Response Delay
Range:
10001. ms*
[11. - 10001. ms]
O-37 Maximum Inter-Char Delay
Range:
25.00 ms*
[0.00 - 35.00 ms]
O-50 Coasting Select
Option:
[0]
Digit Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-52 DC Brake Select
Option:
[0]
Digit Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
Function:
Parity and Stop Bits for the protocol par. O-30 Protocol using the Drive Port. For some of the protocols,
not all options will be visible. Default depends on the protocol selected.
Function:
Specify the minimum delay time between receiving a request and transmitting a response. This is used
for overcoming modem turnaround delays.
Function:
Specify the maximum permissible delay time between transmitting a request and receiving a response.
Exceeding this delay time will cause control word time-out.
Function:
Specify the maximum permissible time interval between receipt of two bytes. This parameter activates
time-out if transmission is interrupted.
Function:
Select control of the coasting function via the terminals (digital input) and/or via the network.
Activates Start command via a digital input.
Activates Start command via the serial communication port or network option module.
Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
Activates Start command via the network/serial communication port OR via one of the digital inputs.
Function:
Select control of the DC brake via the terminals (digital input) and/or via the network.
Activates Start command via a digital input.
Activates Start command via the serial communication port or network option module.
Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.
Activates Start command via the network/serial communication port OR via one of the digital inputs.