at 3 to 5 feet (1 to 1.5 meters) from the floor as per the
requirements of the Canada building codes and the nitrogen
dioxide monitors should be installed at 50% of the ceiling
height and above the vehicle height. If the exhaust pipes
of diesel vehicles are below the vehicles, then the nitrogen
dioxide monitors should be installed at 3 to 5 feet (1 to 1.5
meters) from the floor. In all cases the monitors must be
installed above obstructions blocking circulation of air in
front of the monitors; example, maintenance garages in
automobile dealerships where tool chests, work tables and
storage racks typically line all walls.
3. Heavier than air and will concentrate near the floor; - HFCs,
HCFCs, propane, chlorine, most organic vapors (consult
Opera). Install 1-2 feet (30cm to 50cm) from floor.
For all types of monitors avoid drafts, obstacles, aerosols, silicones.
Place sensors in the center of its coverage area as much as
possible.