BAC Trillium Series Rigging, Installation, Operation & Maintenance Manual

BAC Trillium Series Rigging, Installation, Operation & Maintenance Manual

Adiabatic products
Hide thumbs Also See for Trillium Series:

Advertisement

TrilliumSeries™ Adiabatic Products
RIGGING, INSTALLATION, OPERATION & MAINTENANCE MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for BAC Trillium Series

  • Page 1 – TrilliumSeries™ Adiabatic Products RIGGING, INSTALLATION, OPERATION & MAINTENANCE MANUAL...
  • Page 2 NOTICE • BAC units are typically installed immediately after shipment and many operate year round. However, if the unit is to be stored for a prolonged period of time either before or after installation, certain precautions should be observed.
  • Page 3: Table Of Contents

    Table of Contents RIGGING, INSTALLATION, OPERATION & MAINTENANCE » TRILLIUMSERIES™ ADIABATIC PRODUCTS PART 1 Unit Description PART 5 Detailed Component Maintenance Unit Overview Pre-Cooler Pad and Water System Maintenance Water Distribution System Maintenance PART 2 Rigging Strainer and Pump Maintenance Sump and Water Collection Maintenance Safety Fan and Motor Maintenance...
  • Page 4: Unit Description

    TRILLIUMSERIES™ ADIABATIC PRODUCTS Unit Description Unit Overview Detail A, TSDC Shown Detail B. TSDC2 Shown Figure 1a. TrilliumSeries™ Adiabatic Condenser (TSDC Shown) Figure 1b. TrilliumSeries™ Adiabatic Condenser (TSDC2 Shown) WWW. B A LT IM ORE A IRCOIL.COM...
  • Page 5 Coils: TrilliumSeries™ Adiabatic Producs have either microchannel, or tube/fin coils. The coils are designed to be corrosion resistant, minimize refrigerant or fluid charge, allow for thermal expansion, and be easy to inspect and clean. Whisper Quiet Fan(s): The fans have integrated electronically commutated motors (ECMs). Unit Description These motors have embedded speed control and are highly efficient.
  • Page 6: Part 2 Rigging

    Read all dangers, warnings, cautions, notices, and notes detailed in the margins. death, and/or property damage. Lifts must be performed by qualified riggers following BAC published Rigging Instructions and generally Pre-Rigging Checks accepted lifting practices. The...
  • Page 7 (max 1/16”/ft for the TSDC2 and undertaken, open the access hatch TSDF2). Anchor bolts must be provided by others, BAC recommends 3/4” bolt SAE J429 and check to ensure no water, snow, Grade 5, ASME A325 Type 1 or equivalent.
  • Page 8: Layout Guidelines

    Layout Guidelines TrilliumSeries™ Adiabatic Products must be located to ensure an adequate supply of fresh air to the coils. The axial fan(s) are not equipped to overcome external static pressure. When units are located adjacent to walls or in enclosures, care must be taken to ensure the discharge air is not deflected and recirculated back to the air intakes.
  • Page 9: Rigging

    Rigging Model Number TSDC-xxx-3 1’-6” 2’-0” Layout Guidelines TSDC-xxx-6.2 2’-4” 2’-11” TSDC-xxx-9.6 3’-0” 3’-8” Rigging TSDC-xxx-12.4 3'-6" 4'-0" TSDx2-xxx-12.4 2'-8" 4'-6" TSDx2-xxx-18.6 3'-8" 5'-6" TSDx2-xxx-24.8 4'-3" 6'-2" TSDx2-xxx-31.0 4'-7" 6'-8" TSDx2-xxx-37.2 5'-3" 7'-0” TSDx2-xxx-43.4 5'-7" 7'-3" Table 1. Minimum Wall Separation Distance Rigging Refer to Table 2 and Figure 4 for each unit’s required minimum spreader bar length “W1”...
  • Page 10 Lifts must be performed by qualified Figure 4a. TSDC Lift (TSDC-xxx-9.6 Shown) Figure 4b. TSDC2 and TSDF2 Lift (TSDC2-xxx-24.8 Shown) riggers following BAC published Rigging Instructions and generally accepted lifting practices. The use of supplemental safety slings...
  • Page 11 Rigging Rigging Figure 8. TSDx2-xxx-24.8 Side View (8 Fan) Figure 9. TSDx2-xxx-31.0 Side View (10 Fan) Figure 10. TSDx2-xxx-37.2 Side View (10 Fan) Figure 11. TSDx2-xxx-43.4 Side View (14 Fan) W WW.BALTIMOREAIR C OIL.C O M...
  • Page 12: Prolonged Outdoor Storage

    Prolonged Outdoor Storage TrilliumSeries™ Adiabatic Products are shipped wrapped. If the unit is going to remain in NOTICE: BAC units are typically outdoor storage in excess of three months prior to installation, remove the strech-wrap and installed immediately after tarp and follow the storage recommendations below.
  • Page 13: Part 3 Installation

    12 psi for water, 10 psi for CO , 1 psi for NH and 3 psi for HFCs. Contact BAC block the door opening of the for special selections that may fall outside of these parameters.
  • Page 14 Refrigerant Piping for Multiple Units See Figures 13a and 13b for the refrigerant piping connections for multiple units: • All valves and piping shown to be field provided and installed if necessary. • These piping diagrams show the arrangement of multiple TrilliumSeries™ Adiabatic Condensers.
  • Page 15: Refrigerant Connection

    Installation Piping Guidelines Refrigerant Connection Refrigerant Piping for Multiple When piping the unit, route the water pipes down or to the side so that there is a clear Units landing area in front of the unit for accessing the control panel and access hatch(es) in Piping Guidelines compliance with NEC regulations.
  • Page 16 • For units with the water monitoring option, a water regulator will be provided with the unit which will be shipped loose inside the basin. The regulator must be installed before the make up valve and must be sized according to Figure 16 on page 16. If multiple units are ordered one water regulator should be installed per unit.
  • Page 17 Installation Water Connection Auto-Discrete Valve Water Piping 3/4" FPT Make Up Valve 1 1/2" MPT Overflow (Factory Supplied on the Unit) NOTES FOR FIGURES 8A AND 8B: 3/4" FPT Make Up Valve 1 1/4" FPT Dump/Drain Valve 1. Only valves labeled factory (Factory Supplied on the Unit) (Field provided and installed, if necessary) supplied are provided with the...
  • Page 18: Ammonia Installation Instructions

    Installation of the Pressure Regulating Valve As part of the Water Monitoring option, a pressure regulating valve (PRV) is supplied. Follow the instructions for installation. The valve must be installed on straight rigid pipe 7.5” (19 cm) from the make-up valve, refer to the diagram below for more information. Direction of Flow Set to 20 psi Minimum of 20 Inlet...
  • Page 19: Wiring And Electrical Information

    10.5 13.1 TSDC-xxx-6.2 15.3 19.1 TSDC-xxx-9.6 20.1 25.1 TSDC-xxx-12.4 19.4 24.3 TSDx2-xxx-xxx-12.4 NOTE: For other voltages, contact 28.2 35.3 TSDx2-xxx-xxx-18.6 your local BAC Representative. 46.3 TSDx2-xxx-xxx-24.8 45.8 57.3 TSDx2-xxx-xxx-31.0 54.6 68.3 TSDx2-xxx-xxx-37.2 63.5 79.3 TSDx2-xxx-xxx-43.4 230V TSDC-xxx-3 17.8 22.2 TSDC-xxx-6.2 25.9...
  • Page 20 Controls Connections be supported separately from the The controls wiring should be provided in a separate conduit from any power wiring. BAC unit. Do not penetrate the unit for recommends penetrating the control panel from the bottom or side panel observing standards.
  • Page 21 BAC Controller Side Rack Controller (or BMS) Side Carel Read/ Data Modbus Modbus Index Description Write Variable Name Type TCP/IP BACNet SNMP pressure sensor signal pressure_disp_um 30002 30002 1.3.6.1.4.1.9839.2.1.2.1.0 Outside Air Temperature oa_t_disp 30003 30003 1.3.6.1.4.1.9839.2.1.2.2.0 customer fan speed signal...
  • Page 22 BAC Controller Side Rack Controller (or BMS) Side Carel Read/ Data Modbus Modbus Index Description Write Variable Name Type TCP/IP BACNet SNMP Low Speed Thursday Start Minute LSMThurStrtMin 40240 45032 AV1031 1.3.6.1.4.1.9839.2.1.3.31.0 Low Speed Friday Start Minute LSMFriStrtMin 40241 45033 AV1032 1.3.6.1.4.1.9839.2.1.3.32.0...
  • Page 23 BAC Controller Side Rack Controller (or BMS) Side Carel Read/ Data Modbus Modbus Index Description Write Variable Name Type TCP/IP BACNet SNMP At least one alarm is present for the Zhiel-Abegg Al_Present_ZA11 10030 10030 BV29 1.3.6.1.4.1.9839.2.1.1.29.0 fan 11 At least one alarm is present for the Zhiel-Abegg...
  • Page 24 BAC Controller Side Rack Controller (or BMS) Side Carel Read/ Data Modbus Modbus Index Description Write Variable Name Type TCP/IP BACNet SNMP ZAFan1Disabled ZAFan1Dis 00066 00066 BV65 1.3.6.1.4.1.9839.2.1.1.65.0 ZA Fan16 Disabled ZAFan16Dis 00067 00067 BV66 1.3.6.1.4.1.9839.2.1.1.66.0 ZA Fan15 Disabled ZAFan15Dis...
  • Page 25: Controls Setup For Microchannel Coils

    Installation Controls Setup for Microchannel Coils (TSDC Only) Controls Setup for Microchannel Coils The TrilliumSeries™ Adiabatic Condenser is the most efficient product in its class and as such it has very unique characteristics that need to be taken into account when integrated into a traditional refrigeration system.
  • Page 26: Unit Operation

    Unit Operation Start-Up TrilliumSeries™ Adiabatic Products are shipped fully wrapped. If the unit is going to NOTE: BAC offers Factory Start-Up remain in outdoor storage in excess of three months prior to installation, remove the shrink and commissioning which adds an wrap and follow the storage recommendations on page 10.
  • Page 27 This option monitors the amount of purged from the Condenser given the following conditions: • The pressure regulating valve provided by BAC is properly field installed and set to 20. W WW.BALTIMOREAIR C OIL.C O M...
  • Page 28 • The pressure of the incoming water is 25 psi or greater on a pipe (¾” for TSDC, 1” for TSDC2 and TSDF2). • There are no interruptions of water delivery when the unit is on Pre-Cooler Mode. • The controller is properly set up. •...
  • Page 29 Unit Operation Start-Up Setting the Parameters for the Water Monitoring Option Water Meter Set-up Pre-Cooler Pad Water Flow NOTES FOR FIGURE 18: 1. Change the pressure by rotating the knob Figure 19. Make-up Pressure Balancing Valve 2. Gauge Flow Balancing Valves for Pumps •...
  • Page 30: Modes Of Operation

    Modes of Operation TrilliumSeries™ Adiabatic Products will operate in two basic modes: Dry Mode and Pre-Cooler Mode. In Dry Mode, the water pump will be off and the unit will operate as an air-cooled condenser or fluid cooler. During Pre-Cooler Mode, the unit will use a pump to deliver water over the Pre-Cooler Pads, making the unit operate as an adiabatic condenser or fluid cooler.
  • Page 31 Cleansing Circulation Unit Operation TrilliumSeries™ Adiabatic Products utilizes a patented process in Pre-Cooler Mode to manage the water: maximizing Pre-Cooler Pad wetting while minimizing water consumption Modes of Operation and maintaining hygiene. This process is called Cleansing Circulation. Dry Mode In this process, water enters the unit and is circulated throughout, never remaining still.
  • Page 32 EcoFlex™ Controls BAC’s exclusive EcoFlex™ Controls allow for the TrilliumSeries™ Adiabatic Product to operate in the mode of operation specific for your job conditions without you having to think about it. Each unit is shipped from the factory with your specific climate conditions and preferences in mind.
  • Page 33 Fan Control Unit Operation Every fan will run at the same speed at all times. The fans are connected to each other via ModBus RS485 and controlled using one of these three methods. Water Saver Logic Modes of Operation and Energy Saver Logic will need to be pre-ordered as extra devices and configuration are Pre-Cooler Mode added at the factory: EcoFlex™...
  • Page 34: Winter Operation

    The unit capacity will be affected during the Self-Clean Cycle. The amount of air passing through the coils will be lower than in normal operation, and BAC recommends enabling this feature during low load periods of the day. The unit comes preset to operate the Self-Clean Cycle at 5:45 am for three minutes.
  • Page 35: Discrete Spray Connection

    50°F (10°C). Contact your local BAC Representative for guidelines on the installation of an emergency coil drain system. Discrete Spray Connection The discrete spray connection offers a water by-pass connection in case of pump failure.
  • Page 36: Auto-Discrete Backup Spray System

    Auto-Discrete Backup Spray System The Auto-Discrete Backup Spray System provides a backup water system for adiabatic cooling in case of component failure. The system senses if the pump, make-up valve, or float switch fails, and if so, disables the pump and triggers a backup supply of water to spray over the Pre-Cooler Pads.
  • Page 37: Ecoflex™ Controls Operation

    • Head Pressure Control Package: The TrilliumSeries™ Adiabatic Product can regulate the fan speed by monitoring the refrigerant inlet pressure. This option uses a pressure sensor which is furnished by BAC but installed by others in the field. For information on modes of operation, refer to page 26.
  • Page 38 EcoFlex™ Controls Features Control Panel Disconnect Switch WARNING: Incoming power lines to the disconnect switch remain energized. Take proper electrical precautions when working near Controller Display Inside energized equipment. Figure 29. EcoFlex™ Controls Panel (TSDC Shown) Temperature Sensor (Below the Panel) •...
  • Page 39: Detailed Component Maintenance

    TRILLIUMSERIES™ ADIABATIC CONDENSER Detailed Component Maintenance Recommended Maintenance Intervals Semi Inspect and clean as necessary: Start-Up Monthly Quarterly Annually Annually Inspect general condition of the unit and check unit for unusual noises or vibrations Inspect sump Flush water distribution system Clean pump strainer(s) Inspect Pre-Cooler Pads Check operation of make-up valve and drain valve...
  • Page 40 Pre-Cooler Pad Maintenance The Pre-Cooler Pads, which act as air filters and as such protect the coil from fouling, can catch airborne debris. An inspection is recommended monthly and should focus on: • Signs of excessive fouling and scaling of the Pre-Cooler Pads. •...
  • Page 41: Pre-Cooler Pad And Water System Maintenance

    Detailed Component • Reinstall the pads in reverse order: Maintenance – TSDC: Note that one of the Pre-Cooler Pads is smaller than the others and must be returned to the designated location. Ensure the smaller pad is installed per the location indicated on the yellow label.
  • Page 42: Strainer And Pump Maintenance

    Strainer and Pump Maintenance The strainer at the pump is sized to keep debris out of the water distribution system, however if cleaning is necessary, both the pump and strainer can be cleaned during adiabatic operation. However, before performing any maintenance on the pumps beyond DANGER: Do not perform any service cleaning, cut the power to the pumps in the electrical panel first.
  • Page 43: Fan And Motor Maintenance

    Detailed Component Maintenance Strainer and Pump Maintenance Sump and Water Collection Gutters Maintenance Figure 35. Water Collection Gutters as seen with Pre-Cooler Pads Removed (TSDC2 and TSDF2 Only) Fan and Motor Maintenance Coil Maintenance Fan and Motor Maintenance TrilliumSeries™ Adiabatic Producs use axial fan(s) with variable speed, electronically commutated motors and as such require little maintenance.
  • Page 44: Water Treatment

    Pre-Cooler Pads should be cleaned and/or changed more frequently. To further optimize water use and lengthen pad life, consider ordering the Water Monitoring Package from your local BAC Representative or enabling the Water Saver Logic. EcoFlex™ Controls Maintenance NOTE: Refer to page 28 for more information on EcoFlex™...
  • Page 45 • OA Temp Setpt: This is the temperature at which the Pre-Cooler mode is initiated. The settings range is from 40°F (4.4°C) up to 120°F (48.9°C). BAC presets all units according to weather data for each region and optimizes them for your location.
  • Page 46 Controls Appendix for details on menu navigation. Software Verification for a pCO Controller If a BAC Factory Technician is troubleshooting the controller/program over the phone, they may ask for the software version. To provide them with the information, follow these steps from the control panel screen: •...
  • Page 47 “LOGS.DWL”. The datalog file will be converted using EcoFlex™ Controls the pCO Manager software. Maintenance – Already installed on the BAC USB flash drive, the pCO Manager software is used for Forced Overnight Dry Mode data conversion on the computer.” Software Verification for a 3.
  • Page 48: Part 6 Troubleshooting Guide

    Ensure water is being supplied to the make up valve (green valve on the left). No Water Supply If there is a faulty make up valve, contact your local BAC Representative for a replacement. To check for a faulty sump float, manually raise and lower the float to ensure functionality.
  • Page 49 If your unit has a bleed valve, partially open it. This is a substitute for increasing the Pads duration of the daily drain time, mentioned above. Ensure the drain valve opens and closes 100%. Otherwise, contact your local BAC Faulty Drain Valve Representative for a replacement.
  • Page 50: Appendix A Ecoflex™ Controls

    Appendix: EcoFlex™ Controls The BAC TrilliumSeries™ Adiabatic Product controller is the brains of the unit and manages all the peripherals. At lower ambients, the TrilliumSeries™ Adiabatic Product will act like an air cooled condenser or cooler with variable speeds. At higher ambients, the TrilliumSeries™...
  • Page 51 By pressing Esc, the main menu is shown. The main screen has six buttons: Appendix a: EcoFlex™ Controls Button Name Description This button will illuminate red when Menus an alarm is present in the unit; by Alarm Main Menu pressing it, the display will show the alarm description.
  • Page 52 • Status: Goes back to the default Status screen as described on page 47. • Technician: See page 49 for more information. • Factory: This menu is password protected and only available for BAC factory personnel. WWW. B A LT IM ORE A IRCOIL.COM...
  • Page 53 Technician Menu Appendix a: EcoFlex™ This menu is password protected (1703) and provides access to several submenus that Controls allow the user to make changes on the settings of the unit and test every control. It also allows the user to place the valves, pump or fans in manual mode. The technician menu Menus has four submenus described below.
  • Page 54: Datalogging

    2. Information: This submenu allows the user to view the software version, the BIOS, and the dates of the latest update. 3. Manual Control: This submenu allows the user to manually control the valves, the fans, the pump, and all other analog and digital inputs and outputs. Note, after 15 minutes in inactivity, the controller will revert back into automatic operation of the components.
  • Page 55 Default Adjustable Type Screen Name Description Value Range Comments Time & Date — — — — Outside Air — — — — Temperature Fan Speed Manually adjust fan speed — 0-100% — Dry Mode - Pre-Cooler Mode - Mode of Operation —...
  • Page 56 Default Adjustable Type Screen Name Description Value Range Comments Diagnostics Mode - Technician Menu Continued Fan Speed Manually adjust fan speed 0-100% — Conductivity Conductivity of basin water (0-2000μS). Only present w/ "Water Monitoring Package" (See page 28) 120 sec TSDC Duration of the periodic flush CAUTION: Lowering this value may result in scaling the unit.
  • Page 57: Danfoss

    The settings shown below for Danfoss and Emerson CPC are recommended starting settings based on BAC’s experience with TrilliumSeries™ Products in the field. However, all sites are different and may require additional tuning. Please contact BAC for additional assistance if required.
  • Page 58 Step 5. Program as: Air cooled, Single Fan, Sat Cond Step 6. PG DN and set Minimum speed 1.0%, set Temp, Ambient Temp, Ramp Stages, set Min cond T Maximum speed 100.0%. per customer spec or rack design, set Max cond T per customer spec or rack design, and set the Condenser Delta T per wet bulb design TD.
  • Page 59 Appendix b: Danfoss and Emerson Danfoss Step 11. Go back to the Main Menu and select Step 12. Select the Rack. Refrigeration. Step 13. Select Condenser. Step 14. Select Settings, starter setting: Linear Factor 2.0, Sensitivity 4.0. If saturated condensing temp swings more than plus or minus a few degrees F then increase Sensitivity to reduce swing.
  • Page 60: Emerson

    Emerson NOTE: If you are using a blend gas like R-407A in this example you may want to find a gas that follows the correct curve for the bubble.  CPC’s conversion does not do Dew & Bubble it just splits the difference.  So for the SAT conversion your conversion will always be off by half the glide. ...
  • Page 61 Appendix b: Danfoss and Emerson Emerson Step 3. The Advanced tab: PID settings should be entered into this tab as shown above. W WW.BALTIMOREAIR C OIL.C O M...
  • Page 62 Factory Authorized Parts online. All Cooling • Strainer Replacement Tower Parts are shipped second day and • Spare Fans carry a full 1-year warranty backed by BAC. • Spare Coils To purchase parts online, visit • and more! www.CoolingTowerWorld.com today.
  • Page 63 COOLING TOWERS CLOSED CIRCUIT COOLING TOWERS ICE THERMAL STORAGE EVAPORATIVE CONDENSERS HYBRID PRODUCTS PARTS & SERVICES w w w . B a l t i m o r e A i r c o i l . c o m 7600 Dorsey Run Road, Jessup, MD 20794 ›...

This manual is also suitable for:

Trillium tsdc2Trillium tsdcTrillium tsdf2

Table of Contents