•PMV (Pulse motor valve) wiring
PMV wiring connection from Dx-Controller to Dx-PMV kit is as follows.
Terminal
number
Colour
PMV1
PMV2
L01
L07
RED
L02
L08
BRN
L03
L09
WHI
L04
L10
YEL
L05
L11
ORG
L06
L12
BLU
■Wiring in case of large normal coil and split/interlaced coil
•Normal Coil Type (Large coil, 28, 32ton)
In case of 28 and 32 ton coil (Normal coil), two Dx-PMV kit is connected in parallel and controlled by PMV1 port
(L01 to L06) and PMV2 port (L07 to L12) on Dx-Controller. These two PMVs move in synchronization.
•Split face / Interlaced
Group control setting is necessary in Dx-Controller (DN code : 14).
RBM-
A0121GUL
RBM-
A0301GUL
A1921GUL
A0601GUL
A0961GUL