MOUNTING
Hole dimensions
Fig. 1
For correct installation, observe the dimensions of
the templates shown in the illustration (Fig.1).
Installation note
eView LT104
The panel on which the Integrated Controller and
horizontal
Control Panel is mounted has to have the following
characteristics:
• be sufficiently stiff and strong so that it does not
bend during use;
• be between 1 and 6 mm thick, to allow the
fastening of the device with the terminals
supplied;
Protection against infiltrations of water
eView LT121
horizontal
The Control Panel offers, first of all, a degree of
protection of IP65.
It is therefore possible to install the device in
particularly dusty environments or areas subject to
water spray without problem:
• the compartment in which the device is housed
also has to be dust and waterproof;
• the panel on which the device is installed must be
perfectly smooth and flat on the front;
• the hole in the panel must scrupulously respect
the dimensions indicated;
eView LT150
• the device has to be fastened tightly to the panel,
horizontal
to allow the gasket fitted at the back to ensure
water tightness.
Vibration
The Control Panel can support vibrations up to
150 Hz:
Fig. 2
• from 5 to 9 Hz: sinusoidal 3.5 mm constant;
• from 9 to 150 Hz: sinusoidal with acceleration
equal to 1 G.
Should the device be mounted on a support that
exceeds these limits it is necessary to envisage
a system for the suspension and mitigation of the
vibration.
Minimum spaces for ventilation
The temperature of the compartment that
houses the Control Panel must not exceed,
55 °C.
Figure 2- Free spaces for ventilation shows the
minimum free distances recommended in the
120°
installation of the device in a closed compartment.
Positioning
The Control Panel has to be positioned in order to
guarantee the following conditions:
• the screen must not be directly lit by the sun or
particularly bright light sources.
If necessary, screen direct rays, using an
antiglare shutter for example;
• there must be no sudden temperature changes;
• there must be a low explosion risk: it can
be connected to elements that operate in
environments with a hazardous atmosphere
(flammable or explosive) only through appropriate
and suitable types of interface, compliant to the
safety standards in force;
• low presence of magnetic fields
The angle of the controller must be between 45°
and 120°, as shown in figure (Fig. 3).
Fastening to the panel
Insert the Control Panel into the panel, connect
the 4 terminals supplied to the device and tighten
the screw until the device is fastened tightly to the
panel. (Fig.4).
TECHNICAL DATA
Operating voltage
eView LT104
Current draw
vertical
(at 24 VDC)
Power dissipation
POWER SUPPLY
Protections
Connection
Ethernet port (ETH)
eView LT121
vertical
KEY & LED port
RS-232 port (optional)
RS-485 port (optional)
CONNECTIONS
CAN port (optional)
eView LT150
vertical
USB port
Ethernet
COMMUNICATION
PROTOCOLS
CAN
Modbus
Size (diagonal)
Format
Pixel resolution
Screen area (L x H)
Colors
DISPLAY
Luminosity
Contrast
Backlighting
Fig. 3
Visual angle
Access to software
CONFIGURATION
procedures
ELEMENTS
Touch screen calibration Via software on product
30°
CONTROL
Touch screen
ELEMENTS
Diagnostics
VIEWING
ELEMENTS
Type and frequency
MICROPROCESSOR
Fig. 4
System
MEMORY
Mass
Mass extension
Operating temperature
Storage temperature
AMBIENT
Relative humidity
CONDITIONS
Vibrations
ASSEMBLY
PROTECTION LEVEL
WEIGHT
EMC
(electromagnetic
CE STANDARDS
compatibility)
* SD card not supplied. Available as accessory
eView LT104
eView LT121
eView LT150
24 VDC ±25%
700 mA max
1000 mA max
1100 mA max
17 W max
24 W max
26.5 W max
Polarity inversion
Short circuit
3-pin polarized removable connector
Screw terminals, max cable section 2.5 mm
2
Number of channels: 2 max (1 optional)
Connector: RJ45
Velocity: 10 / 100 / 1000 Mbit/s
Signals: green connection LED, yellow data LED
Connector: RJ45; Standard: USB2.0
Connettore: DB9 M; Velocità: 1.2kbit/s...115kbit/s
Optically isolated
Connector: DB9 M
Speed: 9 kbit/s ... 19 kbit/s
Terminations and polarization: internal, selectable with jumper
Optically isolated
Connector: DB9 M
Speed: 20, 50, 100, 125, 250, 500, 1000 kbit/s, default 500 kbit/s
Termination: internal, selectable with jumper
Number of ports: 2 max; Connector: type A; Standard: USB 2.0
Protection: overload
FTP (File Transfer Protocol) Modbus TCP/IP Master/Slave
Ethercat Master; GDNET Master
CANopen Master
Modbus RTU Master/Slave
10,4"
12,1"
15"
4:3
800 × 600
1024 × 768
211,2 × 158,4 mm
246,0 x 187,5 mm
304,1 × 228,1 mm
256 K / 18 bit
16 M / 24 bit
400 cd/m
450 cd/m
500 cd/m
2
2
2
500:1
1500:1
White LEDs
White LEDs
life 30.000
life 50.000
ore @ 25 °C
ore @ 25 °C
Horizontal: 70° - 70°
Horizontal: 89° - 89°
Horizontal: 70° - 85°
Vertical: 50° - 60°
Vertical: 89° - 89°
Vertical: 70° - 85°
16-position rotary switch
4-wire resistive technology
PW LED (yellow): power supply on
RN LED (green): PLC program state
LED E1 (red): HW Watchdog state
LED E2 (red): PLC program error
ATOM E640 1 GHz
ATOM E660, 1.3 GHz
512 MB, DRAM type DDR II
2 GB Flash memory
SD Card Slot *
0 ... +55 °C (as per IEC 68-2-14)
-20 ... +70 °C (as per IEC 68-2-14)
max 95% RH non condensing (as per IEC 68-2-3)
5 to 9 Hz: sine constant 3.5 mm
10 to 150 Hz: sine acceleration 1G
Built-in, in control boards or panels
IP 65 on front panel (as per IEC 68-2-3)
1,650 kg
2,300 kg
2,850 kg
Conforms to Directive 2014/30/EU
EN61131-2: Programmable controllers
Part 2: Equipment requirements and tests.
eView LT104 / LT121 / LT150
code 81697B - 09/2017 - ENG
QUICK INSTALLATION GUIDE
Side 1
Warnings and safety
Mounting
Technical data
Side 2
Connections
Dimensions
GEFRAN spa
via Sebina, 74 - 25050 Provaglio d'Iseo (BS)
Tel. 03098881 - fax 0309839063- Internet: http://www.gefran.com
WARNING and SAFETY
While all the information contained in this manual has been carefully checked, Gefran S.p.A. accepts
no responsibility for the possible presence of errors or for damage to persons and/or property caused
by the improper use of the manual.
Gefran S.p.A. also reserves the right to make changes to the contents and form of this manual and to the charac-
teristics of the devices illustrated at any time and without prior warning.
The installation of the devices illustrated in the manual must be carried out by qualified technicians in compliance with
the laws and standards in force and in agreement with the instructions contained in the manual.
If the eView LT is used in applications with the risk of damages to persons, machinery or materials, its use in conjunc-
tion with alarms is essential.
It is advisable to envisage the possibility of checking the intervention of the alarms during regular operation.
Before interacting with the Control Panel, the operator must receive full training in the procedures of operation, emer-
gency, diagnosis and maintenance of the system.
More information on the device and on the procedures of installation, maintenance and use can be found in the
installation manual and use eView LT, freely downloadable from the site www.gefran.com.
NOTES ON ELECTROMAGNETIC COMPATIBILITY:
CE: Conformity EMC (electromagnetic compatibility) in compliance with Directive
EN61131-2: Programmable controllers
Part 2: Equipment requirements and test.
Graphic simbol
Indicates contents of sections, general instructions, notes, and other points to which the reader's attention needs to be
called.
Indicates a particularly delicate situation that could affect the safety or correct operation of the controller, or an instruction
that MUST be followed to prevent hazards.
eView LT
Control panel
LV
2014/30/EU.

Advertisement

loading

Summary of Contents for gefran eView LT Series

  • Page 1 PW LED (yellow): power supply on If necessary, screen direct rays, using an Gefran S.p.A. also reserves the right to make changes to the contents and form of this manual and to the charac- VIEWING RN LED (green): PLC program state antiglare shutter for example;...
  • Page 2 < 1 V; For the entry in service of the device (configuration and loading the application program) Please refer to the • the ohm resistance is < 6 Ω. installation manual and use GF_Project Vx, freely downloadable from the site www.gefran.it.

This manual is also suitable for:

Eview lt104Eview lt121Eview lt150