Leuze electronic ASM1 Connecting And Operating Instructions page 28

As-i safety monitor
Hide thumbs Also See for ASM1:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 23
Configuration interface
RS 232
Inputs and outputs
"Start" input
Input of "external device
monitoring circuit" (EDM)
Message output
"safety on"
Safety output
Continuous thermal
current (max.)
Safeguarding
Overvoltage category
Environmental data
Operating temperature
Storage temperature
Protection class
28
9600 baud, no parity, 1 start bit, 1 stop bit, 8 data
bits
Optical coupling input (high active),
input current approx. 10mA at 24V DC
Optical coupling input (high active),
input current approx. 10mA at 24V DC
PNP transistor output, 200mA,
short-circuit and polarity-reversal protection
Potential-free make contact,
max. contact load:
ASM/1, ASM1E/1 and ASM2E/1:
max. total current for all output switching ele-
ments: 6A
i.e. output circuit 1: 3A per output switching el-
ASM/2, ASM1E/2 and ASM2E/2:
max. total current for all output switching ele-
ments: 8A
i.e. output circuit 1: 3A per output switching
output circuit 2: 1A per output switching
or output circuit 1: 2A per output switching
output circuit 2: 2A per output switching
External with max. 4A slow blow
3, for rated operating voltage 300V AC
acc. to VDE 0110 part 1
-20 ... +60°C
-30 ... +70°C
IP 20
ASM
1A DC-13 at 24V DC
3A AC-15 at 230V AC
ement
element
element
element
element

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asm1eAsm2e

Table of Contents