TROUBLE
Generator will not start via
remote panel or other source
Engine does not crank from
local controller
Engine cranks but doesn't start
Engine Starts but shuts down
after a few seconds
Engine Starts but genset not
producing Voltage
For all other trouble shooting issues please contact one of our dealers on our website.
www.powertechgenrators.com
TROUBLESHOOTING
POSSIBLE CAUSE
Generator is not in "auto" mode
Remote connection plug is not
connected
Battery is low or terminals are
dirty.
Crank circuitry wiring improperly
connected.
Cranking fuse blown
Out of fuel.
Fuse Blown
Fuel relay damaged
Fuel System lost prime
See failure on controller LCD
Display
Main breaker is in the "off"
position
Visually inspect all Generator
Output leads for connectivity
or scan the QR code below.
PTI-25-30-T4F Operators Manual
SUGGESTED ACTION
Put Generator in Auto mode via
controller
Reconnect Remote control Plug
Clean terminals and re-charge
battery.
Replace battery if necessary.
Refer to engine control wiring and
check crank connections.
Replace fuse with new of identical
size
Check fuel level, add fuel if
necessary.
Replace fuse in control box
Check fuel relay and replace if
damaged.
Use Primer on top of fuel filter
Turn Main Breaker to the "on"
position
.