acutherm THERMA-FUSER EL Manual page 6

Ddc interoperable linear vav diffuser
Table of Contents

Advertisement

Forces the EL into a lower
energy consumption mode.
For example, an opened
Energy
window could close the
Hold-Off
diffuser in the cooling mode or
cause the EL to go to the
unoccupied setpoint if in the
heating mode
This input network variable is
Terminal
to be used for the trouble
Command
shooting purpose by
Input
manufacturer.
CO2
Reserved for future use.
Application
The EL uses
Mode
'nciHeatCoolMode' instead
2
This variable consists of three fields: state, percent, and flow.
Valid range
State : HVO_OFF, HVO_POSITION, HVO_FLOW_VALUE, HVO_PERCENT, HVO_OPEN, HVO_CLOSE,
HVO_MAXIMUM, HVO_MINIMUM, HVO_NULL
Percent:
Reserved for future use. Do not change from factory default setting.
Flow:
Reserved for future use. Do not change from factory default setting.
Note: Input network variables have higher priority than configuration variables.
Example: the EL diffuser will use the value of nviSetPoint (if this value is valid/non-default) as set point instead of
nciSetPnts.
Output Network Variables
Function
Description
Space
Reports current space
Temperature
temperature.
Reports the supply air
Supply Air
temperature to the network.
Temp
Reports EL status.
Combines the operating
mode, capacity of heating
Unit Status
and cooling used and any
indication of alarms
present.
Informs the network of the
Effective
effective setpoint when the
Setpoint
setpoint is changed.
Reports what the EL flow
Flow
rate is.
Current
Reports the current energy
Energy
consumption state of the
Hold-Off
EL.
State
See Energy Hold-Off
Reports energy use as a
Terminal
function of percentage of
Load
maximum flow setting and
supply air temperature.
nviEnergyHoldOff
nviTermCmdIn
nviCO2
nviApplicMode
Symbol On Screen
Default value
(SCPTs, SNVTs)
nvoSpaceTemp
Current room temp
nvoSupplyAirTemp
Current SA temp
HVAC_OFF, 0.000,
nvoUnitStatus
0.000, 0.000, 0.000,
0.000, 0
nvoEffectSetPt
Current set point
nvoBoxFlow
Current flow
0.0 0 ( 2 fields
nvoEnergyHoldOff
separated by a
space)
nvoTerminalLoad
0.000
0.0 0 ( 2 fields
separated by a
0 to 100%, 0 or 1
space)
<blank>
N/A
Do not change from
32767
factory default setting.
HVAC_AUTO
See nciHeatCoolMode
Range Available
10 – 49°C
(50 – 120°F)
10 – 49°C
(50 – 120°F)
3
See below
50 – 95°F (10 – 35°C)
See Performance Guide
0 to 100%, 0 or 1
-163.84 % TO 163.84 %
6