Advertisement

Minimum
Reserved for future use.
Flow
Minimum
Reserved for future use.
Flow
Standby
Duct Area
Reserved for future use.
CO2 Set
Reserved for future use.
point
Input Network Variables
Function
Description
Allows the EL to connect to a
Space
space temperature sensor
Temperature
other than the one installed in
the EL.
Allows the temperature
setpoint for the occupied and
Temperature
standby modes to be changed
Setpoint
via the network. It is used to
reset the temperature rather
than change them.
Shifts the temperature control
point via the network. It is
typically bound to a
supervisory node providing
Setpoint
outside air temperature
Offset
compensation or to an
external wall diffuser having a
relevant setpoint knob.
Operates only on occupied
and standby setpoints.
Commands the EL diffuser
into different occupancy
Occupancy
modes. It is typically set by a
supervisory node.
Allows the EL to be used with
Duct Inlet
another mfgr's inlet
Temperature
temperature sensor
VAV Manual
Commands the controller into
Override
a manual mode
Commands the EL into
Emergency
different emergency modes.
Command
It is typically set up by a
supervisory node.
Allows the EL to be used with
another manufacturers flow
Flow
sensor located on the
network.
SCPTminFlow
0
SCPTminFlowStby
0
SCPTductArea
0
nciCO2Threshold
5000
Symbol On Screen
Default value
(SCPTs, SNVTs)
327.67°C
nviSpaceTemp
(621.806°F)
327.67°C
nviSetPoint
(621.806°F)
No offset =
nviSetPtOffset
32°F/0°C
nviOccCmd
OC_NUL
327.67°C
nviDuctInTemp
(621.806°F)
nviManOverride
HVO_OFF, 0.000, 0
nviEmergCmd
EMERG_NORMAL
65535 l/s
nviBoxFlow
(138862 cfm)
Do not change from
factory default setting.
Do not change from
factory default setting.
Do not change from
factory default setting.
Do not change from
factory default setting.
Range Available
0 –327.67°C
(0 – 621.806°F)
10 – 35°C
(50 – 95°F)
-10°C to 10°C
(14°F to 50°F)
OC_OCCUPIED,
OC_UNOCCUPIED,
OC_BYPASS,
OC_STANDBY,
OC_NUL
10 – 49°C
(50 – 120°F)
2
See below
EMERG_NORMAL,
EMERG_PRESSURIZE,
EMERG_DEPRESSURIZE,
EMERG_PURGE,
EMERG_SHUTDOWN,
EMERG_NUL
0 – 65535 l/s
(0 – 138862 cfm)
5