Cooper Lighting Sure-Lites EUX Installation Instructions Manual page 2

Universal edge lit exit ac only
Table of Contents

Advertisement

Available languages

Available languages

Installation Instructions for the EUX Universal Edge Lit Exit – AC Only
4. Determine where supply wires will be brought into
the fixture. There are knockouts in each endcap on
the side of the housing, and a hole between the
hanger bars. If the hole between the hanger bars is
to be used, remove the two screws holding the cover
plate and the hanger bars, discard the plate, and then
replace the screws and hanger bars.
5. Install the housing using the hanger bars. The hanger
bars can be extended up to 25.5" , and are designed
to be nailed or screwed to studs, clipped onto the
T-grid of a suspended ceiling, or be suspended from
wires. If the hanger bars need to be configured
perpendicular to the fixture, the hanger bar brackets
can be attached at the ends of the fixture using the
screws provided (See Figure 3).
Hanger
Bar
Assembly
Housing
6. Adjust the fixture to accommodate the thickness of
drywall, plaster, or ceiling tile to be used. The notches
and markings on the hanger bar holders correspond
to the material thickness (See Figure 4).
Hanger Bars
Adjusted for 5/8"
Thick Drywall
Figure 4
7. Connect power supply and ground in accordance with
NEC and local codes. Wire connections are as follows:
Ground to Green Lead, Neutral to White Lead, 277V
line to Orange Lead (if used), 120V line to Black Lead
(if used). Cap unused Line Lead. (See Schematic)
Figure 5
Wire in Wiretrap
2
Cover
Plate
Figure 3
Installation Instructions for the EUX Universal Edge Lit Exit – AC Only
8. If the fixture is to be wall mounted, first, loosen the
set screw on the back of the pivot housing. Then
remove the locking clip by sliding it to the end of the
pivot housing (See Figure 6). Rotate the pivot housing
90 degrees, and then replace the locking clip. Tighten
the set screw.
Locking
Clip
Figure 6
9. Remove the trim assembly from the installation hook.
Slide the trim assembly through the trim cover so
that it can be installed between the trim assembly
and the ceiling or wall.
10. Replace the screws holding the trim assembly to the
housing.
11. Lens is provided in a separate box. Apply chevrons
and background as needed. Snap lens into place.
NOTE: If using the lens with the default transparent
background (instead of the provided white or mirror
backgrounds) it must be installed only where there is
adequate color contrast between the sign legend and
the interior wall finish behind the sign, to provide for
sufficient visibility.
12. Turn on power to fixture.
For Surface Installation:
1. Turn off power supply.
2. Remove the two screws securing the hanger bar
brackets and hanger bars. Remove the hanger bar
assemblies.
3. Determine if the fixture will be mounted on the ceiling,
wall, or end mounted.
• For wall or ceiling mount, attach the canopy over the
hole in the center of the housing using the screws
used to hold the hanger bar brackets (See Figure 7).
Figure 7
049-242
ADX141173
www.cooperlighting.com
Pivot
Housing
Adpater
Plate
Canopy
Housing

Advertisement

Table of Contents
loading

Table of Contents