Product Description
Leviton Cat. No. ODS15-ID, Wall Switch Occupancy Sensor, uses Passive Infrared
(PIR) detection technology to monitor a room for occupancy through a segmented
lens. This specialized lens divides the field of view into sensor zones. When a person
passes into or out of a sensor zone, the sensor detects motion and switches the
lights ON. The lights will remain ON as long as there is an occupant moving through
the sensor zones. ODS15-ID can also be programmed to vacancy mode
(Manual ON/Auto OFF) for installations where manual ON switching is required for
Title 24 applications. The ODS15-ID provides a 180° field of view with a maximum
coverage area of approximately 1100 square feet. The maximum sensing distance
in front of the sensor is 30-40 feet, and 15-20 feet on either side. A "minor motion"
zone detects small body movements and allows the lights to stay ON even though
a person may not be moving or walking around the room. The remainder of the field
of view, the "major motion" zone, exhibits a lesser degree of sensitivity and requires
larger movements. Simple configuration can also be applied using push-button
setup for several popular preconfigured options. ODS15-ID is also equipped with a
photocell for daylighting which is programmable using the Leviton Smart Sensor App.
Before Installation
• Installs into standard single gang wall boxes.
• Supports multi-gang installations.
• Ivory, light almond, black, red, and gray faceplates are available with a color
change kit (sold separately).
• Decora
®
wallplate not included.
• Controls lighting loads and plug load control up to 15A.
FOR OPTIMAL PERFORMANCE:
The ODS15-ID sensor lens establishes dozens of zones of detection. The sensor
is sensitive to the heat emitted by the human body. In order to trigger the sensor,
the source of heat must move from one zone of detection to another. The device is
most effective in sensing motion across its field of view, and less effective sensing
motion towards or away from its field of view. Keep this in mind when selecting
the installation location. Note that occupancy sensors respond to rapid changes
in temperature, so care should be taken NOT to mount the device near a climate
control source (i.e., radiators, air exchanges, and air conditioners). Hot or cold drafts
will look like body motion to the device and will trigger it if the unit is mounted too
close. It is recommended to mount the occupancy sensor at least 6 ft away from
a climate control source. In addition, it is also recommended NOT to mount the
occupancy sensor directly under a large light source. Large wattage bulbs (greater
than 100W incandescent) give off a lot of heat and switching the bulb causes a
temperature change that can be detected by the device. Mount the occupancy
sensor at least 6 ft away from large bulbs. If it necessary to mount the device closer,
lower the wattage of the bulb directly overhead.
Horizontal
Beam Diagram
15-20 ft
4.6-6.1 m
10 ft
3 m
0
10 ft
3 m
15-20 ft
4.6-6.1 m
20 ft
6.1 m
Installation
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit
breaker or fuse and test that power is off before wiring!
1.
Strip wires 3/4 in and connect as per wiring diagram. Ensure wires are firmly
attached and there is no exposed copper.
Blue
Black
Load
Green
Ground
White
2.
Gently place the wires and your device into the wall box and attach with
screws provided.
3.
If desired, change switch color. (Sold separately.)
4.
Restore power and test ON/OFF operation. Locator light should be ON when
switch is in the OFF state.
5.
Install Decora wallplate (not included).
6.
ODS15-ID is designed to work and be fully functional right out of the box,
settings can be adjusted using the Leviton Smart Sensor App or simple push
button programming.
Smart Wallbox Sensors:
INSTALLATION INSTRUCTIONS
Vertical
Beam Diagram
40-48 ft
12.2-14.6 m
20 ft
6.1 m
Major motion coverage
1100 ft^2 (102m^2)
Minor motion coverage
400 ft^2 (37.2m^2)
30-40 ft
9.1-12.2m
Hot (Black)
White
Line
120/277 VAC,
50/60Hz
Neutral (White)
15A Switching ON/OFF
Cat. No. ODS15-ID
CAUTION
• For indoor applications only.
SAVE THESE INSTRUCTIONS.
7.
Using the Leviton Smart Sensor App or push button programming, you can
now configure the sensor to your preferred settings. (Leviton Smart Sensor
App, downloadable from Google Play™ or the Apple App Store®, using any
Bluetooth™ enabled Android™ or iOS Device). Operating mode, sensor
sensitivity, and sensor timeout can be quickly adjusted. For more advanced
settings such as daylighting and nightlight configuration, the Leviton Smart
Sensor App will need to be used for setup and adjustments.
PIR Lens and
Nightlight
Programming:
can be performed
by pressing button
(per install instructions)
Operation
PUSH-BUTTON: ODS15-ID has a push button switch that will toggle the lights ON
or OFF. When mode is set to Auto ON / Auto OFF, the lights will automatically turn
ON when occupancy is detected and will turn OFF automatically after occupancy is
no longer detected and the timeout has expired. If mode is set to Manual ON / Auto
OFF, the lights will only turn ON when the push button switch is pressed; the lights
will turn OFF automatically after occupancy is no longer detected and the timeout
has expired. If the lights are ON, the lights can be turned OFF when the button is
pressed. The lights will stay OFF (regardless of motion detected) until the timeout
expires. After the timeout expires, the lights will turn ON when the next motion is
detected. This is useful for slide or film presentations.
NOTES:
• The Motion Indicator light will blink RED for 1 second each time motion
is detected.
• In Manual ON mode, the button must be pressed to turn the lights ON. In the
absence of motion, the unit will time out and turn the lights OFF.
Configuration and Programming
1.
The ODS15-ID Sensor is designed to work out of the box in default settings.
Changes to these settings and additional product configuration can be performed
using the Leviton Smart Sensor App, downloadable from Google Play™ or the
®
Apple App Store
, using any Bluetooth™ enabled Android™ or iOS Device.
a. To pair to device using the Leviton Smart Sensor App:
i.
Press and hold the ON/OFF button for 2-5 seconds; when the light behind
the PIR lens blinks BLUE, release the button.
30-40 ft
ii.
Open the Leviton Smart Sensor App and connect to the device.
9.1-12.2m
iii. The device can also be found by scanning for nearby devices; devices can
be identified in the app to confirm you are connected to the right sensor.
b. Use the Leviton Smart Sensor App to:
i.
Set operating mode to Auto ON / Auto OFF (default) or
Manual ON / Auto OFF.
ii.
Adjust the sensitivity of the sensor to increase or decrease field of
view coverage area pending the room size (100% for larger spaces
approaching 1100 sq ft).
iii. Adjust timeouts (amount of time lights/load will turn OFF after occupancy is
no longer detected).
iv. Activate the night light and its operating mode; selection of custom night
light color.
v.
Add daylighting and select target levels for daylighting.
vi. Set a security code to lock configuration.
vii. See Leviton Smart Sensor App for additional settings and other
programming options.
2.
If the installer does not have access to a Bluetooth enabled Android or iOS
Device, popular preset product configuration can also be made using simple push
button commands:
a. If wall plate is attached, remove first. With the wallplate removed, pinch sides
of sensor near bottom tabs to release front cover of sensor.
PK-A3316-10-00-2A
ENGLISH
Motion Indicator
Light
Photocell and
Locator Light
ON/OFF
Button

Advertisement

loading

Summary of Contents for Leviton ODS15-ID

  • Page 1 ODS15-ID can also be programmed to vacancy mode (Manual ON/Auto OFF) for installations where manual ON switching is required for Title 24 applications. The ODS15-ID provides a 180° field of view with a maximum coverage area of approximately 1100 square feet. The maximum sensing distance in front of the sensor is 30-40 feet, and 15-20 feet on either side.
  • Page 2 LIMITED 5 YEAR WARRANTY AND EXCLUSIONS Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date.