Connect The Cable To The Tank Unit; Fixing Of Power Supply Cable And Connecting Cable; Wire Stripping And Connecting Requirement; Connecting Requirement - Panasonic WH-ADC0309J3E5UK Installation Manual

Air-to-water hydromodule + tank
Hide thumbs Also See for WH-ADC0309J3E5UK:
Table of Contents

Advertisement

Cold water supply
Inlet pipe
Drain valve
(fi eld supply)
Tee Joint
(fi eld supply)
1. Connect the tundish and route the discharge pipe as shown
above. Tundish should be visible and positioned away from frost
environment and electrical components.
2. The tundish should be fi tted vertically and as close to the safety
device as possible and within 600mm of the device.
3. The tundish should be visible to users and positioned away from
electrical devices.
4. The discharge pipe from the tundish should be terminate in a safe
place where there is no risk to person nearby to the discharge, be
of metal construction and:
A) Be at least one pipe size larger than the nominal outlet size of
the safety device unless its total equivalent hydraulic resistance
exceeds that of a straight pipe 9m long. Bends must be taken
into account in calculating the fl ow resistance.
B) Have a vertical section of pipe at least 300mm long, below the
tundish before any elbows or bends in the pipework.
C) Be installed with a continuous fall.
D) Have discharges visible at both the tundish and fi nal point of
discharge.
CONNECT THE CABLE TO THE
4
TANK UNIT
WARNING
This section is for authorized and licensed electrician only. Work
behind the Control Board Cover 3 secured by screws must only
be carried out under supervision of qualifi ed contractor, installation
engineer or service person.

Fixing of Power Supply Cable and Connecting Cable

1. Connecting cable between Tank Unit and Outdoor Unit shall be
approved polychloroprene sheathed fl exible cord, type designation
60245 IEC 57 or heavier cord. See below table for cable size requirement.
Model
Tank Unit
WH-UD03JE5, WH-UD05JE5 4 x min 1.5 mm
WH-ADC0309J3E5UK
WH-UD07JE5, WH-UD09JE5 4 x min 2.5 mm
Ensure the colour of wires of Outdoor Unit and the terminal no.
are the same to the Tank Unit respectively.
Earth wire shall be longer than the other wires as shown in the
fi gure for the electrical safety in case of the slipping out of the
cord from the Holder (Clamper).
2. An isolating device must be connected to the power supply cable.
Isolating device (disconnecting means) should have minimum
3.0 mm contact gap.
Connect the approved polychloroprene sheathed power supply
1 cord and power supply 2 cord and type designation 60245
IEC 57 or heavier cord to the terminal board, and to the other
end of the cord to isolating device (Disconnecting means).
See below table for cable size requirement.
Pressure reducing valve
(fi eld supply)
Safety valve
Expansion vessel
(fi eld supply)
<600mm
Tee Joint
(fi eld supply)
Tundish
(fi eld supply)
Connecting
Cable Size
Outdoor Unit
Model
Tank Unit
Outdoor Unit
WH-UD03JE5,
WH-UD05JE5
WH-ADC0309J3E5UK
WH-UD07JE5,
WH-UD09JE5
3. To avoid the cable and cord being damaged by sharp edges, the cable
and cord must be passed through a bushing (located at the bottom
of Control Board) before terminal board. The bushing must be used
and must not be removed.
Terminals on the Outdoor Unit
Colour of wires (Connecting cables)
Terminals on the Tank unit
(Power Supply Cord)
Terminals on the isolating devices
from power supply (Disconnecting
means)
Connecting Cable
Terminal screw
M4
M5
*1 - Earth wire must be longer than other cables for safety reasons

WIRE STRIPPING AND CONNECTING REQUIREMENT

Wire stripping
No loose strand
when insert
Conductor
fully insert
ACCEPT

CONNECTING REQUIREMENT

For Tank Unit with WH-UD03JE5, WH-UD05JE5, WH-UD07JE5,
2
WH-UD09JE5
2
The equipment's Power Supply 1 complies with IEC/EN 61000-3-2.
The equipment's Power Supply 1 complies with IEC/EN 61000-3-3
and can be connected to current supply network.
The equipment's Power Supply 2 complies with IEC/EN 61000-3-2.
The equipment's Power Supply 2 complies with IEC/EN 61000-
3-11 and shall be connected to suitable supply network, with the
following maximum permissible system impedance Z
ohm () at the interface. Please liaise with supply authority to
ensure that the Power Supply 2 is connected only to a supply of
that impedance or less.
Power
Isolating
Supply
Cable Size
Devices
Cord
2
1
3 x min 1.5 mm
15/16A 30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A 30mA, 2P, type AC
1
3 x min 2.5 mm
2
25A
30mA, 2P, type A
2
2
3 x min 1.5 mm
15/16A 30mA, 2P, type AC
L
N
L
N
1
1
L
N
L
N
1
1
Power Supply 1 Power Supply 2
RCCB/ELCB
Terminal Board
*1
Holder (Clamper)
Power Supply Cable
Tightening torque cN•m {kgf•cm}
157~196 {16~20}
196~245 {20~25}
Indoor/outdoor
connecting
terminal board
5mm or more
(gap between wires)
Conductor
Conductor not
over insert
fully insert
PROHIBITED
PROHIBITED
Recommended
RCD
1
2
3
1
2
3
Tank Unit/
Outdoor Unit
connection
= 0.352
max
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ud03je5Wh-ud05je5Wh-ud07je5Wh-ud09je5