Vector OPA2-MOD Manual page 7

Programmable operation terminal for modbus
Table of Contents

Advertisement

Operation state, symbols & alarms
Address
Type
100
8bit
2000
bit
2001
bit
2002
bit
2003
8bit
2004
bit
2005
bit
2006
bit
2007
bit
2008
bit
2009
bit
2010
bit
2011
16 bit
2012
8bit (ASCII)
2013
8bit (ASCII)
2014
8bit (ASCII)
2015
8bit (ASCII)
2016
bit
2017
bit
2018
bit
Doc: 70-00-0290, V1.0 R0, Date: 20160208
Subject to alteration
R/W
Contents
R/W
"Something changed" flag. Contains the zone ID value whenever a setpoint
gets changed in that zone or the number 10 if operation mode or state of
digital inputs changed.
Needs to be reset by the master through a write command.
R/W
Operation state ON / OFF
0 = OFF
1 = ON
R/W
Operation state occupied / unoccupied
0 = Unoccupied
1 = Occupied
R/W
Maximum number of fan speeds (1...3)
R/W
Actual fan speed
R/W
Show fan symbol(0)
R/W
Show alarm symbol (0)
R/W
Show alarm string (0)
R/W
Show heating symbol (0)
R/W
Show cooling symbol (0)
R/W
Show comfort operation mode symbol (0)
R/W
Show standby operation mode symbol (0)
R/W
Show arrow 0-10 LSb = Arrow 1 on the left (0)
R/W
text string alarm letter 1:
R/W
text string alarm letter 2:
R/W
text string alarm letter 3:
R/W
text string alarm letter 4:
R/W
A flag to define where the alarm text shall be displayed
0 = nowhere
1 = large digits
2 = small digits
R/W
Show time symbol (0)
R/W
Show manual override symbol (0)
© Vector Controls GmbH, Switzerland
OPA2-MOD(-H)
Configuration
-
A
L
A
Page 7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Opa2-mod-h40-50 001440-50 0053

Table of Contents