Display Zone - Vector OPA2-MOD Manual

Programmable operation terminal for modbus
Table of Contents

Advertisement

Display zone 1

Address
Type
5000
Selection
5001
16 bit signed
5002
Selection
5003
Selection
5004
16 bit signed
5005
16 bit signed
5006
16 bit signed
5007
16 bit signed
5008
16 bit signed
5009
8 bit
5010
8bit (ASCII)
5011
8bit (ASCII)
5012
8bit (ASCII)
5013
8bit (ASCII)
Display zone 2 – 5
As above with following register addresses:
Group 2 = 6000 – 6013
Group 3 = 7000 – 7013
Group 4 = 8000 – 8013
Group 5 = 9000 – 9013
Doc: 70-00-0290, V1.0 R0, Date: 20160208
Subject to alteration
R/W
Contents
R/W
Contents of large digits:
0 = empty
1 = text string group 1
2 = value
3 = setpoint (Comfort/Standby depending on operation mode)
4 = Alarm text
5 = internal NTC
6 = external NTC
7 = humidity value
8 = digital input 1.
9 = digital input 2.
R/W
Value of large digits
R/W
Unit of digits
0 = no unit
1 = %
2 = °C
3 = Pa
R/W
Contents of small digits:
0 = empty
1 = text string group 1
2 = value
3 = setpoint (Comfort/standby depending on operation mode)
4 = Alarm text
5 = internal NTC
6 = external NTC
7 = humidity value
8 = digital input 1.
9 = digital input 2.
R/W
Comfort setpoint
20.0
R/W
Standby setpoint
20.0
R/W
Setpoint step
0.1; 0.5; 1.0; 2.0; 5.0
R/W
Low setpoint limit
16.0
R/W
High setpoint limit
30.0
R/W
Vertical bar 0-10
0
R/W
Text string letter 1
R/W
Text string letter 2
R/W
Text string letter 3
R/W
Text string letter 4
© Vector Controls GmbH, Switzerland
L
P
1
OPA2-MOD(-H)
Configuration
Page 10