Download Print this page
Vector TLC3-FCR-2T-U Engineering Manual

Vector TLC3-FCR-2T-U Engineering Manual

Intelligent fan coilcontroller

Advertisement

Quick Links

TLC3-FCR-2T-U
Intelligent Fan Coilcontroller
Features
The PWM and 3-point floating control option reduces room
temperature fluctuations and energy consumption
Low power energy consumption: < 1W per unit
Temperature control for 2- and 4-pipe fan coil systems.
Automatic fan control for three stage fans.
Cost saving option with Economy functionality and set point
limitations
Control for single stage heating, cooling and fan only operation
modes
Password protected programmable user and control parameters
Setpoint range limitation
o
Access control for setpoints, fan speeds and mode change
o
Access control for heat/cool change and time programs
o
Select your display contents
o
Selectable behavior after return from power failure
o
Temperature display in Celsius or Fahrenheit
Deluxe Version:
Clock and time schedule functions with power failure protection
Blue backlight for LCD
Infrared remote controller option:
With special features for Boost and delayed switching on or off
Applications
Air Only Systems:
Constant Air Volume systems with three stage fans for single or dual duct systems
o
Air/Water Systems:
Fan Coil units for 2-pipe or 4-pipe systems
o
radiator control, chilled ceiling
o
Simple individual room control for hotel rooms, meeting rooms, etc.
PWM or On-Off-Control of 2 spring return valves or 3-point on-off or floating control of one 3-point valve.
General Description
The TLC3-FCR-2T is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-2 features 1 NTC
temperature sensor input and five binary outputs. Three outputs control a fan with low, medium and high fan speeds.
Two binary outputs may be used to control either two spring return or thermal valves or one three point floating valve.
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-2-U can be
configured using the standard operation terminal. No special tools or software is required.
Ordering
Item Name
TLC3-FCR-2R-U-24
TLC3-FCR-2R-U-24-W01
TLC3-FCR-2R-U-D-24
TLC3-FCR-2R-U-D-24-W01
TLC3-FCR-2T-U-120
TLC3-FCR-2T-U-120-W01
TLC3-FCR-2T-U-D-120
TLC3-FCR-2T-U-D-120-W01
TLC3-FCR-2T-U-230
TLC3-FCR-2T-U-230-W01
TLC3-FCR-2T-U-D-230
TLC3-FCR-2T-U-D-230-W01
Selection of valve actuators and fans
Binary auxiliary devices: E.g. fans and on/off valves. Observe switching power as detailed under technical
specifications! Do not connect more than one fan coil unit to one controller.
Doc: 70-00-0203, V3.0 Date: 20121119
Subject to alteration
Item code
Variant
Standard
40-10 0140
Cooling only
40-10 0140-01
Deluxe
40-10 0145
Cooling only
40-10 0145-01
Standard
40-10 0150
Cooling only
40-10 0150-01
Standard
40-10 0155
Cooling only
40-10 0155-01
Standard
40-10 0120
Cooling only
40-10 0120-01
Deluxe
40-10 0121
Cooling only
40-10 0121-01
© Vector Controls GmbH, Switzerland
TLC3-FCR-2T-U Engineering Manual
Power
Features
Fan coil controller with:
24VAC/DC
1 TI int
3 DO (Relay) Fan control
24VAC/DC
2 DO (Relay) Binary valve control
120VAC
Fan coil controller with:
120VAC
1 TI int
3 DO (Relay) Fan control
230VAC
2 DO (TRIAC) Binary valve control
230VAC
mailto:info@vectorcontrols.com
Page 1

Advertisement

loading

Summary of Contents for Vector TLC3-FCR-2T-U

  • Page 1 Binary auxiliary devices: E.g. fans and on/off valves. Observe switching power as detailed under technical specifications! Do not connect more than one fan coil unit to one controller. mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 1 Subject to alteration...
  • Page 2: Technical Specification

    60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) Distance for mounting screws: Horizontal 55 to 60mm (2.2 to 2.4 in.) Vertical: 55 to 93mm (2.2 to 3.7 in.) mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3 Fan speed high Binary output: Heating Valve or OPEN if in 3-point floating mode Binary output: Cooling Valve or CLOSE if in 3-point floating mode mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    Error temperature sensor. The internal temperature sensor may be damaged or not present. Steady: Frost protection is active. Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5  See chapter operation, advanced settings for instructions on how to set the time. Access to time schedules may be disabled with UP-04  mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6 Repeatedly pressing the mode button may activate the following operation modes: HEAT, COOL and FAN ONLY. The mode change may be disabled using the UP parameters. Note: The remote controller is currently only available in °C mode. mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7 Setting of user parameters The TLC3-FCR-2T-U is an intelligent controller and can be adapted to fit perfectly into your fan coil application. The control operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.
  • Page 8: Control Configuration

    Prevents activation of a sequence during a short-term change in temperature in order to protect equipment (with control overshoot for example) mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9 In PWM mode the digital output will be switched on/off once per cycle. The on and off times are calculated according to the control sequence. mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...
  • Page 10 TLC3-FCR-2T-U Engineering Manual Notes: mailto:info@vectorcontrols.com Doc: 70-00-0203, V3.0 Date: 20121119 © Vector Controls GmbH, Switzerland Page 10 Subject to alteration...