Air-Cooled Condenser Data - Vogt TUBE-ICE 03TA Service Manual

Table of Contents

Advertisement

3-12
INSTALLING YOUR TUBE-ICE
Ice Machine Model
Electrical Frequency, Hz.
Recommended Condenser
Total Heat Rejection (BTU/hr)
Fans:
Number
HP, Each
Total CFM
Full Load Amps (FLA):
3 ph., 208/230V, 60 hz.
3 ph., 460V, 60 hz.
3 ph., 200V, 50 hz.
3 ph., 380V, 50 hz.
Weight, lbs.:
Net
Shipping
Operating (Maximum flooded) R-404a
Condenser Dimensions, inches
A (Width)
B (Length)
C (Height)
D (Leg centerline)
E (Leg centerline)
F (Clearance below)
Recommended Line Sizes, OD
Liquid
All lengths and orientations
Discharge Gas
Vertical Up, all lengths
Horiz. or Down, < 75 ft.
Horiz. or Down > 75 ft.
Connections at Condenser:
Liquid (ODV)
Discharge Gas (ODV)
Connections at Ice Machine:
Liquid (ODV)
Discharge Gas (ODV)
4/2/14
®
MACHINE
(See Fig. 3-7)
TABLE 3-4

Air-Cooled Condenser Data

03TA (Standard)
03TA (High Ambient)
60/50
60/50
BNHS02A011
BNHS02A011(12)
157,500 / 144,900
172,500 / 159,700
2
1 1/2
20,500
14.0
7.0
14.0
7.0
580
585
760
765
610
615
45.46"
127"
49.15"
38"
106.15"
20.5"
7/8"
1 1/8"
1 1/8"
1 3/8"
1 1/8"
1 3/8"
1 1/8"
1 1/8"
03TA Service Manual

Advertisement

Table of Contents
loading