OPTIONAL ELECTRIC HEAT
The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single
point terminal block.
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending
into the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and other do not. Refer to Table 14 for
minimum CFM limitations and to Tables 10 through 12 for
electrical data.
TABLE 14: ELECTRIC HEAT MINIMUM SUPPLY AIR
CFM
IMPERIAL
HEATER
UNIT MODEL SIZE, NOMINAL TONS
VOLTAGE
kW
9
18
380/415
24
36
54
METRIC
HEATER
UNIT MODEL SIZE, NOMINAL TONS
VOLTAGE
kW
9
18
380/415
24
36
54
OPTIONAL GAS HEAT
These gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition.
TABLE 15: GAS APPLICATION DATA
Unit
Input (MBH)
Size
Opt.
10
120
090
15
175
120
15
175
150
15
175
Unitary Products Group
10
12.5
MINIMUM SUPPLY AIR CFM
N/A
N/A
3000
3750
3000
3750
3000
3750
3000
3750
10
12.5
MINIMUM SUPPLY AIR CFM
N/A
N/A
1.41
1.76
1.41
1.76
1.41
1.76
1.41
1.76
Output (MBH)
Temp Rise (°F)
96
15-45
140
30-60
140
15-45
140
10-40
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. "National Fuel Gas Code" Z223.1 should be
followed in all cases unless superseded by local codes or gas
utility requirements. Refer to the Pipe Sizing Table 16. The
heating value of the gas may differ with locality. The value
should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a one-inch pipe connection at the entrance
fitting.
FIGURE 21 - SIDE ENTRY GAS PIPING
FIGURE 22 - BOTTOM ENTRY GAS PIPING
OPTIONAL
COIL
GUARD
SHOWN
21