Reader interface

Advertisement

Powering
Trusted Identities
7.
Input power, cabinet tamper, and UPS fault input wiring
The X100 requires 12-24 V DC power. Connect power
with minimum of 18 AWG wire.
Grounding and Bonding: The DC ground or return wire
must be bonded to the Earth Ground of the building,
during installation.
Connect the power ground to earth ground in only ONE
LOCATION within the system. Multiple earth ground
connections may cause ground loop problems and is
not advised.
Observe POLARITY on 12-24 V DC input.
Status LEDs
POWER
LED
ON SELF-TEST
ONLINE
ON then OFF
COMM
ON then OFF
BATT FAIL
ON then OFF
AC FAIL
ON then OFF
TAMPER
ON then OFF
IN 1
ON then OFF
IN 2
ON then OFF
IN 3
ON then OFF
IN 4
ON then OFF
READER 1
ON then OFF
READER 2
ON then OFF
RELAY 1
OFF
RELAY 2
OFF
RELAY 3
OFF
RELAY 4
OFF
*If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1 seconds, otherwise,
the LED is OFF.
6
Heartbeat and Online status. Offline = 1 sec rate, 20% ON. Online encrypted comm .1 sec
ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .3 sec OFF. Waiting
for application download .1 sec ON, .1 sec OFF.
RS-485 Comm status. Indicates communication activity on the SIO communication port.
OFF = Inactive, ON = Active, Flash = Fault.*
OFF = Inactive, ON = Active, Flash = Fault.*
OFF = Inactive, ON = Active, Flash = Fault.*
OFF = Inactive, ON = Active, Flash = Fault.*
OFF = Inactive, ON = Active, Flash = Fault.*
OFF = Inactive, ON = Active, Flash = Fault.*
OFF = Inactive, ON = Active, Flash = Fault.*
Wiegand or C&D mode = Flashes when data is received, either input.
OSDP mode = Flashes when transmitting data.
Wiegand or C&D mode = Flashes when data is received, either input.
OSDP mode = Flashes when transmitting data.
ON = Energized
ON = Energized
ON = Energized
ON = Energized
HID Aero™ X100 Installation Guide
Connect the AC FAIL and BATT FAIL inputs to the
corresponding contacts provided on the power supply.
Connect the TAMPER input to a tamper switch on the
enclosure.
TAMPER, AC FAIL, and BATT FAIL connections are
identical to inputs IN 1 to IN 4 and can be configured
as unsupervised or supervised. See step 4. Input circuit
wiring.
NORMAL OPERATION
PLT-04234, Rev. A.3