Functional Safety KCD2-RR2-Ex1(.SP)

Product Description

2
Product Description
2.1

Function

This isolated barrier is used for intrinsic safety applications.
It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas.
The device supports 2-, 3-, or 4-wire technique depending on the required accuracy.
The input card of the control system measures the same load as if it were connected directly
to the resistance in a hazardous area.
The device is mounted on a 35 mm DIN mounting rail according to EN 60715.
2.2

Interfaces

The device has the following interfaces.
Safety relevant interfaces: input and output
Note!
For corresponding connections see datasheet.
2.3

Marking

Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KCD2-RR2-Ex1(.SP)
2.4

Standards and Directives for Functional Safety

Device specific standards and directives
Functional safety
System-specific standards and directives
Functional safety
IEC/EN 61508, part 1 – 7, edition 2010:
Functional safety of electrical/electronic/programmable electronic
safety-related systems (manufacturer)
IEC 61511-1:2016+COR1:2016+A1:2017
EN 61511-1:2017+A1:2017
Functional safety – Safety instrumented systems for the process
industry sector (user)
Up to SIL 2