Functional Safety HiD2035, HiD2036
Operation
Proof Test Procedure
1. Put out of service the entire safety loop. Protect the safety application by
2. Prepare a test set-up, see figures below.
3. Test the devices. Verify the current values as given in table below.
4. Set back the device to the original settings for the application after the test.
HiD2035, HiD2036, 1oo1 Structure
Step No.
1
2
3
4
5
6
7
8
Table 5.1
Figure 5.1
Channel 2 only for HiD2036
16
means of other measures.
Input value (V)
6
14
14
22
22
30
30
30
Steps to be performed for the proof test
+
1
mA
-
4
+
2
mA
-
5
Zone 0, 1, 2
Div. 1, 2
Proof test set-up for HiD2035, HiD2036
Input value (mA)
1.50
4.00
20.00
10.00
40.00
5.00
25.00
50.00
HiD2036
SL2
SL1
5a
8a
5b
7a
1a
10a
1b
9a
Measured input current (mA)
1.50 ± 0.5
4.00 ± 0.5
20.00 ± 0.5
10.00 ± 0.5
40.00 ± 0.5
5.00 ± 0.5
25.00 ± 0.5
50.00 ± 0.5
Multimeter
(A)
11
+
V
14
-
12
+
V
15
-
1
2